■Output type (1)
The output type is determined by the combination of control mode (MODE) and operation type (TYPE) as follows.
Control mode (MODE)
MAN, CMB, CMV, LCM, LCA, LCC
AUT, CAB
CAS, CCB, CSV
■Loop stop processing (2)
The following processing is performed according to the SPA status of the alarm detection (ALM).
SPA status
1
0
■SV count-up processing (3)
SV count-up is performed every execution cycle (T) according to the following expression.
SV'=SV+T
■MVPGS operation (4)
MV
operation is shown below.
PGS
Output type
Control mode (MODE)
MV
operation
PGS
Processing at SV'>SV
n
■Output processing (5)
The output processing conditions are shown below.
Condition
MV
>MH
PGS
MV
<ML
PGS
Others
*1 If the MHI or ERRI of the disable alarm detection (INH) is set to 1, the output upper limit alarm (BB2) and the MHA of the alarm detection
(ALM) are set to 0.
*2 If the MLI or ERRI of the disable alarm detection (INH) is set to 1, the output lower limit alarm (BB3) and the MLA of the alarm detection
(ALM) are set to 0.
11 PROCESS CONTROL INSTRUCTIONS
1336
11.3 Control Operation Instructions
Processing details
The loop stops.
When the loop stops or the number of operation constant break points is 0, the following operations are performed and the S.PGS
instruction ends.
• The output value (BW) is held.
• All of the output alarm bits (BB1, BB2, and BB3) are set to 0.
• The MHA and MLA of alarm detection (ALM) are set to 0.
• The control mode (MODE) is set to MAN.
The loop runs. When the loop runs, "SV count-up processing (3)" is performed.
SV<SV1
SV<SV
SV
n-1
n
0: Mode shift
SV
MV
Restart method
Manual
MAN, CMB, CMV, LCM, LCA, LCC
BW
BB2, MHA
MV
0
n
MV
0
n
MV
0
n
Operation type (TYPE)
0
1
Hold type
AUT, CAB
MV1
-
MV
MV
n
n-1
×(SV'-SV
)+MV
-
n-1
SV
SV
n
n-1
MAN
Last value
Last value
After SV setting, change to
the MANAUT mode.
Automatic
AUT, CAB, CAS, CCB, CSV
BB3, MLA
BW
0
MV
=MH
n
0
MV
=ML
n
0
MV
=MV
n
Operation
Operation stop with the current SV and MV
Hold type operation
Return type operation
Cyclic type operation
Return type
Cyclic type
CAS, CCB, CSV
n-1
MAN
No mode shift
0
0
Last value
MV1
Change to the MANAUT
Automatic restart
mode.
BB2, MHA
*1
1
0
0
PGS
BB3, MLA
0
*2
1
0