■TIMER_CONT_FB_M/TIMER_CONTHFB_M
• This is a retentive timer that measures the on time of a variable. When (s1) turns on, measurement of the current value
starts. There are two retentive timers: low-speed (TIMER_CONT_FB_M) and high-speed (TIMER_CONTHFB_M) retentive
timers.
• The measurement starts from (s3)1 to 1000ms (0.1 to 100ms for the high-speed retentive timer) (variable; set in
parameter). When the value reaches (s2)1 to 1000ms (0.1 to 100ms for the high-speed retentive timer), (d2) turns on. The
measured current value is output to (d1).
• Even when (s1) is off, the on/off states of (d1) and (d2) are held. When (s1) turns on again, the measurement resumes with
the measured value that has been held.
• The unit of measurement (time limit) for the retentive timers is common to both the low-speed timer (TIMER_LOW_FB_M)
and high-speed timer (TIMER_HIGH_FB_M).
• Low-speed retentive timer: Low-speed timer
• High-speed retentive timer: High-speed timer
• The valid setting range of (s2) is 0 to 32767.
• The valid setting range of (s3) is -32768 to 32767. Note that if a negative value is specified, 0 will be used as the initial
value.
• To reset (d1) of a retentive timer, reset (s1) of FB directly.
Ex.
Label name: TIMER_CONT_FB_M_1
[Ladder program]
RST
M0
EN
ENO
d
[ST program]
RST(M0,TIMER_CONT_FB_M_1.Coil)
[Ladder example]
TIMER_CONT_FB_M
X0
Coil
200
Preset
ValueOut
0
ValueIn
Status
[Timing chart]
X0
OFF
D10
0
M10
OFF
Operation error
There is no operation error.
36 COUNTER/TIMER FUNCTION BLOCKS
2000
36.8 Timer Function Block
TIMER_CONT_FB_M_1.Coil
D10
M10
ON
15s
...
1
150
5s
...
151
200
ON

Hide quick links:

Advertisement

Table of Contents
loading