Mitsubishi Electric MELSEC iQ-R Series Programming Manual page 1320

Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

■Input data
Operand: (s1)
Device
Symbol
+0
E1
+1
■Block memory
Operand: (d1)
Device
Symbol
+0
BW
+1
+2
BB
BB1
■Operation constant
Operand: (s2)
Device
Symbol
+0
PN
+1
TRK
+2
SVPTN
11 PROCESS CONTROL INSTRUCTIONS
1318
11.3 Control Operation Instructions
Name
Recommended range
Input value
-999999 to 999999 [%]
Name
Recommended range
Output value
-999999 to 999999 [%]
Operation result
b15
0: |BW|<50%
1: |BW|50%
Name
Recommended range
Operation mode
0: Reverse action
1: Direct action
Tracking bit
0: Tracking not performed
1: Tracking performed
Set value
0 to 3
pattern
b15
(1) Use of set value
Specify whether to use the set value (E2) or not.
0: Used
1: Not used
(2) Set value pattern
Specify whether to use the upper loop MV as the set value (E2) or
not.
0: E2 is the upper loop MV.
1: E2 is not the upper loop MV.
...
b0
...
b0
(2)
(1)
Data type
Standard
Set by
value
Single-precision
User/
real number
system
Data type
Standard
Set by
value
Single-precision
System
real number
16-bit unsigned
System
binary
Data type
Standard
Set by
value
16-bit unsigned
0
User
binary
16-bit unsigned
0
User
binary
16-bit unsigned
3
User
binary

Hide quick links:

Advertisement

Table of Contents
loading