Mitsubishi Electric MELSEC iQ-R Series Programming Manual page 1979

Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Processing details
■Operation processing
When (s) turns on, (d) turns on only for one scan.
■Operation result
1.
Function block without EN/ENO
The operation processing is performed. The operation result is output from (d).
• Timing chart
ON
ON
(s)
OFF
ON
ON
(d)
OFF
OFF
(1)
(2)
(1) (d) turns on at the rising edge of (s).
(2) (d) turns off in the next scan.
2.
Function block with EN/ENO
The execution conditions and operation results will be as follows.
Execution condition
EN
TRUE (executed)
FALSE (not executed)
• Timing chart
ON
EN
ON
(s)
OFF
ENO
OFF
ON
(d)
OFF
(1)
(2)
(1) (d) turns on at the rising edge of (s) while EN is on.
(2) (d) turns off in the next scan.
(3) If EN is off, (d) holds the output value of the last scan.
Operation error
There is no operation error.
ON
ON
ON
ON
OFF
OFF
Operation result
ENO
TRUE
FALSE
ON
ON
ON
ON
ON
ON
ON
OFF
OFF
(d)
Operation result output value
Previous output value
ON
ON
ON
ON
ON
ON
OFF
OFF
(3)
35 EDGE DETECTION FUNCTION BLOCKS
OFF
35.1 Detecting a Rising Edge
35
1977

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents