Mitsubishi Electric MELSEC iQ-R Series Programming Manual page 1670

Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

■Applicable devices
Operand
Bit
X, Y, M, L,
SM, F, B, SB,
FX, FY
*1
(U)
(s1)
(s2)
(d1)
(d2)
*1 Index modification is not available.
■Control data
Operand: (s1)
Device
Item
+0
Completion status
+1
Station number
+2
Send data size
+3
Receivable data size
+4
Receive data size
19 CC-LINK INSTRUCTIONS
1668
19.8 Performing a Message Transmission to a Remote Device Station
Word
J\
T, ST, C, D, W,
SD, SW, FD, R,
ZR, RD
Description
The completion status is stored upon completion of the instruction.
• 0: Completed successfully
• Other than 0: Completed with an error (error code)
Specify the station number of the target station.
Specify the send message data size in bytes.
Specify the maximum size of the device that stores the receive message data in
bytes.
The receive message data size is stored in bytes.
Double word Indirect
U\G, J\,
Z
LT, LST,
U3E\(H)G
LC
Constant
specification
LZ
K, H E
Setting range
1 to 64
1 to 255
0 to 255
Others
(U)
$
Set by
System
User
User
User
System