Ending a block
RST [BL]
RnPCPU
RnPCPU
RnCPU RnENCPU
(Process)
(Redundant)
• The RnCPU and RnENCPU with firmware version "12" or later support this instruction. (Use an engineering tool with version "1.015R" or later.)
• The RnPCPU (process) with firmware version "03" or later supports these instructions. (Use an engineering tool with version "1.020W" or later.)
This instruction deactivates the specified block.
Ladder
(d)
FBD/LD
EN
ENO
d
■Execution condition
Instruction
RST
Setting data
■Description, range, data type
Operand
Description
(d)
Block No. to be deactivated
(Reset (off) target bit device number)
EN
Execution condition
ENO
Execution result
■Applicable devices
Operand
Bit
X, Y, M, L,
J\
SM, F, B, S,
SB, FX, FY
(d)
*1 The BL can be index modified.
Processing details
• This instruction deactivates the specified block independently.
• All the active steps are deactivated and coil outputs are turned off.
• If the block start/end bit of the SFC information device is set, the corresponding bit device turns off.
• If the instruction is executed to an inactive block, the instruction is ignored.
RnSFCPU RnSFCPU
(Standard)
(Safety)
Execution condition
Word
T, ST, C, D, W,
U\G, J\,
SD, SW, FD, R,
U3E\(H)G
ZR, RD
ST
ENO:=RST(EN,d);
Range
Data type
Bit
Bit
Bit
Double word Indirect
Z
LT, LST,
LZ
LC
13 SFC PROGRAM INSTRUCTIONS
Data type (label)
ANY_ELEMENTARY
BOOL
BOOL
Constant
Others
specification
(BL)
K, H E
$
13.1 SFC Control Instructions
13
*1