Ending a block

RST [BL]
RnPCPU
RnPCPU
RnCPU RnENCPU
(Process)
(Redundant)
• The RnCPU and RnENCPU with firmware version "12" or later support this instruction. (Use an engineering tool with version "1.015R" or later.)
• The RnPCPU (process) with firmware version "03" or later supports these instructions. (Use an engineering tool with version "1.020W" or later.)
This instruction deactivates the specified block.
Ladder
(d)
FBD/LD
EN
ENO
d
■Execution condition
Instruction
RST
Setting data
■Description, range, data type
Operand
Description
(d)
Block No. to be deactivated
(Reset (off) target bit device number)
EN
Execution condition
ENO
Execution result
■Applicable devices
Operand
Bit
X, Y, M, L,
J\
SM, F, B, S,
SB, FX, FY
(d)
*1 The BL can be index modified.
Processing details
• This instruction deactivates the specified block independently.
• All the active steps are deactivated and coil outputs are turned off.
• If the block start/end bit of the SFC information device is set, the corresponding bit device turns off.
• If the instruction is executed to an inactive block, the instruction is ignored.
RnSFCPU RnSFCPU
(Standard)
(Safety)
Execution condition
Word
T, ST, C, D, W,
U\G, J\,
SD, SW, FD, R,
U3E\(H)G
ZR, RD
ST
ENO:=RST(EN,d);
Range
Data type
Bit
Bit
Bit
Double word Indirect
Z
LT, LST,
LZ
LC
13 SFC PROGRAM INSTRUCTIONS
Data type (label)
ANY_ELEMENTARY
BOOL
BOOL
Constant
Others
specification
(BL)
K, H E
$
13.1 SFC Control Instructions
13
*1
1427