■Control data
Operand: (s1)
Device
Item
+0
Error completion type
+1
Completion status
+2
Own station channel
+3
Target station CPU type
+4
Target network number
+5
Target station number
+6
Not used
15 NETWORK COMMON INSTRUCTIONS
1456
15.1 Link Dedicated Instructions
Description
...
b15
b8
b7
(3)
0
(2) (1)
(1) Error completion type (bit 7)
Specify whether to set data at completion with an error.
• 0: Do not set data in (s1)+12 and later at completion with an error.
• 1: Set data in (s1)+12 and later at completion with an error.
(2) Arrival check time setting (bit 8)
• 0: 1s units
• 1: 100ms units
(3) Target station address specification method (b15)
• 0: Specify "network No." in (s1)+4, and "station number" in (s1)+5.
• 1: Specify "IP address" in (s1)+4, 5 (Ethernet only)
The completion status is stored upon completion of the instruction.
• 0: Normal
• Other than 0: Error (error code)
Specify the channel to be used by own station. (Page 1450 Range of available
channel numbers)
Specify the CPU type of the target station.
• 0000H: Addressed to target station CPU (control CPU)
• 03D0H: Addressed to control system CPU
• 03D1H: Addressed to standby system CPU
• 03D2H: Addressed to system A CPU
• 03D3H: Addressed to system B CPU
• 03E0H: Addressed to multiple CPU No. 1
• 03E1H: Addressed to multiple CPU No. 2
• 03E2H: Addressed to multiple CPU No. 3
• 03E3H: Addressed to multiple CPU No. 4
• 03FFH: Addressed to target station CPU (control CPU)
[CC-Link IE Controller Network or CC-Link IE Field Network]
Specify the network number (1 to 239) of the target station.
[Ethernet]
■When "0" is specified in bit 15 of (s1)+0
Specify the network number (1 to 239) of the target station.
■When "1" is specified in bit 15 of (s1)+0
Specify the IP address (third and fourth octets) of the target station.
...
b15
b8
b7
• b8 to b15: 3rd octet
• b0 to b7: 4th octet
[CC-Link IE Controller Network]
Specify the station number (1 to 120) of the target station.
[CC-Link IE Field Network]
Specify the station number of the target station.
• 125: Master station
• 126: Master operating station
• 1 to 120: Local station, intelligent device station, submaster station
[Ethernet]
■When "0" is specified in bit 15 of (s1)+0
Specify the station number (1 to 120) of the target station.
■When "1" is specified in bit 15 of (s1)+0
Specify the IP address (first and second octets) of the target station.
...
b15
b8
b7
• b8 to b15: 1st octet
• b0 to b7: 2nd octet
...
b0
0
...
b0
...
b0
Setting range
Set by
0000H
User
0080H
0100H
0180H
8000H
8080H
8100H
8180H
System
1 to 18
User
0000H
User
03D0H to 03D3H
03E0H to 03E3H
03FFH
■(s1)+4
User
Network No.:
1 to 239
■(s1)+5
Station No.:
1 to 120, 125, 126
■(s1)+4, 5
IP address:
00000001H to
FFFFFFFEH
(1 to 4294967294)