■Setting items (arguments)
Setting item
(s1)
Set value (SV)
(s2)
Process value
(PV)
*1
(s3)
Control data
(d)
Manipulated value
(MV)
*1 When auto tuning is not used, the same number of points are occupied as when the step response method is used.
■Setting items (control data)
Operand: (s3)
Device
Item
+0
Sampling time (T
+1
Action setting (ACT)
+2
Input filter constant ()
+3
Proportional gain (K
+4
Integral time (T
+5
Derivative gain (K
+6
Derivative time (T
+7 to +19
These areas are used for internal processing of PID operation, and therefore data cannot be changed.
*1
+20
Input variation (increase) alarm setting
value
*1
+21
Input variation (decrease) alarm setting
value
*1
+22
Output variation (increase) alarm setting
value
Output upper limit setting value
9 PID OPERATION INSTRUCTION
1146
9.2 PID Operation Instruction
Description
Set the set value (SV).
■Auto tuning (limit cycle method)
If the set value for auto tuning differs from that for normal PID control, set a value obtained by adding a bias
value, and then set the SV back to the original value when the auto tuning flag turns off.
Set the input value for PID operation.
■Auto tuning (limit cycle method)
The device areas of 29 points starting from the device specified in (s3) are used.
■Auto tuning (step response method)
 The device areas of 25 points starting from the device specified in (s3) are used when all of the bits 1, 2,
and 5 of (s3)+1 (Action setting (ACT)) are not 0.
 The device areas of 20 points starting from the device specified in (s3) are occupied when all of the bits 1,
2, and 5 of (s3)+1 (Action setting (ACT)) are 0.
■Normal PID control
The user sets the initial manipulated value before execution of the instruction. After execution, the operation
result is stored.
■Auto tuning (limit cycle method)
During auto tuning, the output upper limit value (ULV) or output lower limit value (LLV) is output automatically.
Upon completion of auto tuning, the given MV is set.
■Auto tuning (step response method)
The user sets the step manipulated value before execution of the instruction. During auto tuning, the MV
cannot be changed by the PID instruction.
Description
)
1 to 32767 [ms]
S
Bit 0
0: Direct action
1: Reverse action
Bit 1
0: Input variation alarm disabled
1: Input variation alarm enabled
Bit 2
0: Output variation alarm disabled
1: Output variation alarm enabled
Bit 3
Reserved
Bit 4
0: Auto tuning disabled
1: Auto tuning enabled
Bit 5
0: No output upper/lower limit value setting
1: Output upper/lower limit value setting
enabled
Bit 6
0: Step response method
1: Limit cycle method
Bits 7 to 15
Reserved
0 to 99 [%]
)
1 to 32767 [%]
P
)
1 to 32767 [ 100ms]
I
)
0 to 200 [%]
D
)
1 to 32767 [ 10ms]
D
0 to 32767
0 to 32767
0 to 32767
-32768 to 32767
Remarks
The sampling time must be longer than the operation
cycle of the programmable controller.
Action direction specification
Do not turn on bit 2 and bit 5 at the same time.
Do not turn on bit 2 and bit 5 at the same time.
Auto tuning mode selection
0 = No input filter
0 =  (No integration)
0 = No derivative gain
0 = No derivation
Enabled when the bit 1 of (s3)+1 (Action direction
(ACT)) is 1.
Enabled when the bit 1 of (s3)+1 (Action direction
(ACT)) is 1.
Enabled when the bit 2 of (s3)+1 (Action direction
(ACT)) is 1, and the bit 5 is 0.
Enabled when the bit 2 of (s3)+1 (Action direction
(ACT)) is 0, and the bit 5 is 1.
Number of
occupied
points
1 point
1 point
29 points
 25 points
 20 points
1 point