Mitsubishi Electric MELSEC iQ-R Series Programming Manual page 991

Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Error
Error content
code
2000H
The format of the Unicode text file is incorrect.
2001H
The key setting of the Unicode text file is incorrect.
2002H
The number of characters making up a database name, table name, or
field name exceeds the limit.
2003H
The number of tables exceeds the limit.
2004H
The format of the setting value of the record in the Unicode text file is
incorrect.
2005H
The maximum number of records that can be imported is exceeded.
2006H
An invalid character is included in the database name.
2007H
The format of the row index is incorrect.
2009H
Failed to read data from the Unicode text file.
200AH
Failed to write data to the Unicode text file.
200BH
The number of fields in the Unicode text file exceeds the maximum
number.
200CH
In the Unicode text file, the number of columns set in the field row does
not match that set in another row.
200DH
The number of indexes in the Unicode text file exceeds the maximum
number.
200EH
The number of characters of the main key name in the Unicode text
file, external key name, or index name exceeds the maximum number.
200FH
The database access instruction cannot be executed because the SD
memory card is write-protected. Or, startup of the CPU module
database access (from external device) function from an external
device failed.
2010H
The database access instruction cannot be executed or the CPU
module database access function cannot be executed from an external
device because the SD memory card does not have enough free space
(10M bytes or more).
2011H
The number of characters making up the path of the database exceeds
128.
2020H
The CPUDB folder configuration is incorrect.
2021H
The database is broken.
2023H
Startup of the database failed.
2024H
Suspension of the database failed. Or, the database was suspended
because the SD memory card was removed.
Action
• Check whether the format of the Unicode text file is correct. If not,
correct it.
• Check whether the number of characters in the comment line is
within the range.
Check that an out-of-range value is not set with regard to the key
constraint of the Unicode text file.
• Check that the database name, table name, or field name in the
Unicode text file does not exceed 32 characters.
• Check whether 128 or more tabs are used in a single line.
Check that the number of tables in the Unicode text file does not
*1
exceed 32.
Check that the format of the setting value in the Unicode text file is
correct.
Check that the number of records in the text file does not exceed the
maximum number (100,000).
Check that an invalid character is not included in the database name in
the text file.
Check that the format of the row index is correct.
• Check the status of the SD memory card.
• Check the contents of the Unicode text file.
Check the status of the SD memory card.
Check that the number of fields in the Unicode text file does not exceed
*1
128.
Check the Unicode text file to verify that the number of columns set in
the field row (number of fields) matches that set in another row.
Check that the number of indexes in the Unicode text file does not
exceed the number of table fields.
Check whether the numbers of key name and index name characters
are each 16 or less.
Clear the write protection of the SD memory card.
Secure enough free space of the SD memory card.
Reduce the number of characters making up the path to 128 or less.
• Decrease the number of databases in the CPUDB folder to 32 or
less.
• Delete folders which are not databases in the CPUDB folder.
• Refer to the error database check file (2:\CPUDB\ErrorDB.txt) and
delete a folder which caused the error.
• Create a new database.
• Refer to the error database check file (2:\CPUDB\ErrorDB.txt) and
delete a database which caused the error.
• Power off and on the CPU module or reset it.
• Check the data memory capacity and secure a free space of 1K byte
or more.
• Power off and on the CPU module or reset it.
• Insert the SD memory card again, and power off and on the CPU
module or reset it.