Registering routing information

S(P).RTWRITE
RnPCPU
RnCPU RnENCPU
(Process)
These instructions write routing information in the area with the specified transfer destination network number.
Ladder
(s1) (s2)
FBD/LD
EN
ENO
s1
s2
■Execution condition
Instruction
S.RTWRITE
SP.RTWRITE
Setting data
■Description, range, data type
Operand
Description
(s1)
Transfer destination network number
(s2)
Start device where the write data is stored
EN
Execution condition
ENO
Execution result
■Applicable devices
Operand
Bit
X, Y, M, L,
SM, F, B, SB,
FX, FY
(s1)
(s2)
7 APPLICATION INSTRUCTIONS
1074
7.28 Routing Information Instructions
RnPCPU
RnSFCPU RnSFCPU
(Redundant)
(Standard)
(Safety)
Execution condition
Word
J\
T, ST, C, D, W,
SD, SW, FD, R,
ZR, RD
ST
ENO:=S_RTWRITE(EN,s1,s2);
ENO:=SP_RTWRITE(EN,s1,s2);
Range
1 to 239
Double word Indirect
U\G, J\,
Z
LT, LST,
U3E\(H)G
LC
Data type
Data type (label)
16-bit signed binary
ANY16
Word
ANY16_ARRAY
(Number of elements: 3)
Bit
BOOL
Bit
BOOL
Constant
specification
LZ
K, H E
Others
$