Measuring Time Of The Specified Data - Mitsubishi Electric MELSEC iQ-R Series Programming Manual

Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Measuring time of the specified data

TIMCHK
RnPCPU
RnPCPU
RnCPU RnENCPU
(Process)
(Redundant)
This instruction measures the on time of the device and, if the on time has continued as specified or longer, turns on the
specified device.
Ladder
(s1)
(s2)
(d)
FBD/LD
EN
ENO
s1
d
s2
■Execution condition
Instruction
TIMCHK
Setting data
■Description, range, data type
Operand
Description
(s1)
Device for storing the current value measured (unit:
100ms)
(s2)
Set value for measurement or the device where the set
value for measurement is stored (unit: 100ms)
(d)
Device to be turned on at time-up
EN
Execution condition
ENO
Execution result
■Applicable devices
Operand
Bit
X, Y, M, L,
J\
SM, F, B, SB,
FX, FY
(s1)
(s2)
(d)
RnSFCPU RnSFCPU
(Standard)
(Safety)
Execution condition
Word
T, ST, C, D, W,
U\G, J\,
SD, SW, FD, R,
U3E\(H)G
ZR, RD
ST
ENO:=TIMCHK(EN,s1,s2,d);
Range
Data type
16-bit signed binary
0 to 32767
16-bit signed binary
Bit
Bit
Bit
Double word Indirect
Z
LT, LST,
LZ
LC
7 APPLICATION INSTRUCTIONS
Data type (label)
ANY16
ANY16
ANY_BOOL
BOOL
BOOL
Constant
Others
specification
K, H E
$
7.26 Timing Check Instructions
7
1033

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents