File Register Read/Write Instructions; Reading 1-Byte Data From The File Register - Mitsubishi Electric MELSEC iQ-R Series Programming Manual

Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

7.23

File Register Read/Write Instructions

Reading 1-byte data from the file register

ZRRDB(P)
RnPCPU
RnPCPU
RnCPU RnENCPU
(Process)
(Redundant)
These instructions read the data from the file register with the specified serial byte number.
Ladder
(s)
(d)
FBD/LD
EN
ENO
s
d
■Execution condition
Instruction
ZRRDB
ZRRDBP
Setting data
■Descriptions, ranges, and data types
Operand
Description
(s)
Serial byte number of the file register to be read
(d)
Start number of the device for storing the data that has
been read
EN
Execution condition
ENO
Execution result
■Applicable devices
Operand
Bit
X, Y, M, L,
J\
SM, F, B, SB,
FX, FY
(s)
(d)
RnSFCPU RnSFCPU
(Standard)
(Safety)
Execution condition
Word
T, ST, C, D, W,
U\G, J\,
SD, SW, FD, R,
U3E\(H)G
ZR, RD
ST
ENO:=ZRRDB(EN,s,d);
ENO:=ZRRDBP(EN,s,d);
Range
Data type
0 to 4294967295
32-bit unsigned binary
16-bit signed binary
Bit
Bit
Double word Indirect
Z
LT, LST,
LZ
LC
7 APPLICATION INSTRUCTIONS
7.23 File Register Read/Write Instructions
Data type (label)
ANY32
ANY16
BOOL
BOOL
Constant
Others
specification
K, H E
$
7
995

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents