Processing details
• These instructions read the data of the transfer destination network number specified by (s) from the routing information set
in parameter, and store the information in the device specified by (d) and later.
• If the data of the transfer destination network number specified by (s) is not set in parameter, 0 is stored in the device
specified by (d) and later.
• The following figure shows the data stored in the device specified by (d) and later.
Start device
(d)
(d)+1
(d)+2
• The specification ranges of relay station number are as follows.
Network type
MELSECNET/H
CC-Link IE Controller Network
CC-Link IE Field Network (master station)
CC-Link IE Field Network (local station)
Operation error
Error code
Description
(SD0)
3405H
The value set to (s) is out of the range, 1 to 239.
Item
Relay network number
Relay station number
Dummy
Range
1 to 239
Refer to the following table.
Specification range
1 to 64
1 to 120
Fixed to 125 (The fixed value is stored.)
1 to 120 (The relevant station number is stored.)
7 APPLICATION INSTRUCTIONS
7.28 Routing Information Instructions
7
1073