Processing details
• These instructions calculate the tangent of the angle specified by (s), and store the sign of the operation result in the device
specified by (d) and the operation result in the devices specified by (d)+1 and (d)+2.
(d)
TAN (s) =
(d): Sign
(d)+1: Integral part
(d)+2: Decimal part
• For the value to be specified in (s), set a value from 0 to 360(in the DEG. unit) as a BCD value.
• For the sign of the operation result to be stored in the device specified by (d), 0 is stored when the operation result is
positive and 1 is stored when the operation result is negative.
• The operation result to be stored in the devices specified by (d)+1 and (d)+2 is a BCD value in the range from -57.2901 to
57.2903.
• The operation result is a value whose 5th decimal place is rounded off.
Operation error
Error code
Description
(SD0)
3405H
An out-of-range value is set to (s).
• The specified data is not a BCD value.
• The specified data is out of the range, 0 to 360.
• The specified data is 90 or 270.
7 APPLICATION INSTRUCTIONS
800
7.9 Real Number Instructions
(d)+1
(d)+2
.