Wiring Of Inverter Control Circuit - Mitsubishi Electric FR-A872-P Instruction Manual

Table of Contents

Advertisement

2.6.4

Wiring of inverter control circuit

 Control circuit terminal layout
*1
2
5
4
1 F/C +24 SD
AM
5 10E 10 SE SE
RUN
SU
*1
This terminal operates as terminal FM for the type FM inverter. For the type CA inverter, the terminal operates as terminal CA.
*2
The X10 signal is assigned to terminal MRS in the initial setting.
*3
No function is assigned in the initial setting.
 Wiring method
 Power supply connection
For the control circuit wiring, strip off the sheath of a cable, and use it with a blade terminal. For a single wire, strip off the sheath
of the wire and apply directly.
Insert the blade terminal or the single wire into a socket of the terminal.
1.
Strip off the sheath for the below length. If the length of the sheath peeled is too long, a short circuit may occur with
neighboring wires. If the length is too short, wires might come off.
Wire the stripped cable after twisting it to prevent it from becoming loose. Do not solder it.
2.
Crimp the blade terminal.
Insert wires to a blade terminal, and check that the wires come out for about 0 to 0.5 mm from a sleeve.
Check the condition of the blade terminal after crimping. Do not use a blade terminal of which the crimping is
inappropriate, or the face is damaged.
Blade terminals commercially available (as of January 2017)
• Phoenix Contact Co., Ltd.
2
Cable gauge (mm
)
With insulation sleeve
0.3
AI 0,34-10TQ
0.5
AI 0,5-10WH
0.75
AI 0,75-10GY
1
AI 1-10RD
1.25, 1.5
AI 1,5-10BK
0.75 (two-wire product)
AI-TWIN 2×0,75-10GY
*1
A ferrule terminal with an insulation sleeve compatible with the MTW wire which has a thick wire insulation.
*2
Applicable for terminals A1, B1, C1, A2, B2, C2.
So SOC
SD
SIC
S1 S2 PC
IPF OL FU
PC RL RM RH RT AU
*3
Cable sheath stripping length
Ferrule terminal model
Without insulation sleeve
A 0,75-10
A 1-10
A 1,5-10
A1
B1
C1
A2
B2
C2
STP MRS
RES
SD SD
STF STR JOG
(X10)*2
Damaged
Crumpled tip
For UL wire
AI 0,5-10WH-GB
AI 0,75-10GY-GB
AI 1-10RD/1000GB
AI 1,5-10BK/1000GB
CS
Unstranded
wires
Wires are not inserted
into the sleeve
Crimping tool
*1
name
CRIMPFOX 6
*2
2. INSTALLATION AND WIRING
2.6 Control circuit
1
2
3
4
5
6
7
8
9
10
55

Advertisement

Table of Contents
loading

Table of Contents