Acceleration And Deceleration; Set Points At Multifunction Input; Quitting Commissioning - BONFIGLIOLI ACTIVE CUBE 201 Operating Instructions Manual

Frequency inverter 230 v/400 v, 0.25 kw...132 kw
Hide thumbs Also See for ACTIVE CUBE 201:
Table of Contents

Advertisement

9.2.10.1 Acceleration and deceleration

The settings define how fast the output frequency changes after a reference value change or a start,
stop or brake command.
Parameter
No.
Description
420 Acceleration (Clockwise)
421 Deceleration (Clockwise)
NOTICE
The deceleration of the drive is monitored in the default parameter
Voltage Controller
increase in the DC link voltage during regenerative operation and/or during the braking
process.

9.2.10.2 Set points at multifunction input

Multifunction input MFI1 can be parameterized for a reference value signal in
Operation Mode 3 should only be selected by expert users for drive control via
480 and
Fixed Frequency 2
Operation Mode 452
1 - Voltage Input
2 - Current Input
3 - Digital input
Use multifunction input MFI1 as digital input for slow signals. For rapidly and regularly
changing signals, use a digital input S2IND...S6IND or a digital input of an extension
module EM.
9.2.11

Quitting commissioning

Confirm the "End" display by pressing the ENT key.
The guided commissioning of the frequency inverter is terminated via a reset and
the initialization of the frequency inverter. Relay output X10 reports a fault due to
default setting
inverted).
After successful initialization of the frequency inverter, the factory-set parameter
Actual Frequency
The drive is accelerated to the set
Configurations 110, 111, 410, 411, 430 or 0.00 Hz in Configurations 210, 211, 230,
510) by:
signals at digital inputs S1IND/STOA (STOA) and S7IND/STOB (STOB) and
Start clockwise by rising signal edge at S2IND or
 S tart anticlockwise by rising
signal edge at S3IND
Status signals
160 - Standby Message
12/16
Min.
0.00 Hz/s
0.00 Hz/s
670. The deceleration ramp can be extended in the case of an
481.
voltage signal (MFI1A), 0 V ... 10 V
current signal (MFI1A), 0 ...20 mA.
digital signal (MFI1D), 0 V ... 24 V
Op. Mode Digital Output 3
241 is displayed.
Signals that frequency inverter has been initialized and is ready for
1)
operation.
Operating Instructions ACU
Setting
Max.
Factory setting
9999.99 Hz/s
9999.99 Hz/s
Operation Mode
Function
532 = „103 - Inv. Error Signal" (Inv:
418 (default: 3.50 Hz in
Min. Frequency
5.00 Hz/s
5.00 Hz/s
Operation Mode
452.
Fixed Frequency 1
109