Description of the blocks
4.1 Functions for all blocks
4.1.10.14

Activate fault status for external control system fault

Number of the
Feature
Feature bit purpose
Specify whether the block should switch to the error state at an external process control error
CSF =1.
The default setting is 0.
Bit = 0: Block does not go to error state with process control error CSF = 1.
Bit = 1: Activated: Block goes to error state with process control error CSF = 1.
4.1.10.15

Reset even in locked state

Number of the
Feature
Feature bit purpose
You can specify if it is possible to perform a reset with an active "Protection" or "Motor
protection" type interlock. This can be used, for example, to reset hardware interlocks.
The default setting is 0.
Bit = 0: No reset is possible with a "Protection" type interlock or with active motor protection.
Bit = 1: Reset is possible with a "Protection" type interlock or with active motor protection.
4.1.10.16
Disable Feedback Tracking LocalSetting 2 & 4
Number of the
Feature
Feature bit purpose
To disable the tracking of feedback signals in the "Local" mode setting 2 and 4.
The default setting is 0.
Bit = 0: Calculation of impulse controls in LocalSetting 2 and 4.
Bit = 1: Disable calculation of impulse controls in LocalSetting 2 and 4.
86
bit: 18
bit: 19
bit: 20
Programming and Operating Manual, 06/2017, A5E40899442002A/RS-AA/001