Huawei SmartAX MA5616 Configuration Manual page 159

Multi-service access module
Table of Contents

Advertisement

SmartAX MA5616 Multi-service Access Module
Configuration Guide
The Fe-lithium battery is connected to the input port of the power system through a power cable
and connected to the MA5616 through an RS485 serial port cable. When detecting a Fe-lithium
battery, the MA5616 issues a command to the power system to adjust the voltage. The charging
mode of a Fe-lithium battery is the equalizing mode.
When the mains supply fails, the Fe-lithium battery provides power for the MA5616 to ensure
the normal running of the device in a certain period. When the mains supply recovers, the Fe-
lithium battery stops discharging and starts charging.
Procedure
Step 1 Add the EPS30-4815AF, namely, Power4830.
Run the emu add command to add the Power4830.
Step 2 Configure the parameter of the rectifier unit.
Run the power module-num command to configure the parameter of the rectifier unit.
Step 3 Configure the environment parameters for power supply monitoring.
Run the power environment command to configure the upper and lower alarm thresholds and
measurement thresholds of temperature or humidity for power monitoring. In this manner, the
power module generates alarms when it works in a condition that does not meet the present
requirements.
Step 4 Configure the external extended digital parameter for power supply monitoring.
Run the power outside_digital command to configure the external extended digital parameter
for power supply monitoring.
Step 5 Query configuration parameters and environment parameters of the power system.
Run the display power system parameter command to query configuration parameters of the
power monitoring unit.
Step 6 Run the display power alarm command to query the alarm. Ensure that no alarm (except the
door status alarm) for the monitoring parameter is generated.
Step 7 Save the data.
Run the quit command to quit the Power4830 mode, and then run the save command to save
the data.
Step 8 Configure the Fe-lithium battery monitoring unit.
1.
2.
3.
4.
5.
----End
Issue 04 (2011-10-30)
Run the emu add command to add a Fe-lithium battery monitoring unit.
(Optional) Run the power batteryinstall command to set the time for installing the battery.
Run the display power run info command to query the battery running information, such
as the charging status and remaining power.
(Optional) Run the display power batteryinstalltime command to query the time for
installing the battery.
Run the save command to save the data.
NOTE
The subnode ID of the Fe-lithium battery is invariably 23.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
3 Basic Configuration
148