SmartAX MA5616 Multi-service Access Module
Configuration Guide
Table 3-27 Data plan for configuring the power monitoring through the EPS30-4815AF
Item
EMU
Battery
management
parameters
Charging
parameters of
the battery
Issue 04 (2011-10-30)
Data
Type: Power4830 (Pwr4830)
SN: 2
Subnode ID: 4
NOTE
The hardware DIP switch on the
EPS30-4815AF ranges from 0–31
and therefore the subnode ID ranges
from 0–31. Ensure that the
hardware DIP switch on the
EPS30-4815AF is set the same as
that of the EMU subnode on the
device.
This topic uses value 4 as an
example.
Current-limiting coefficient for
battery charging: 0.15
Interval of battery equalized
charging: 60 days
Number of battery sets: 1
Capacity of the battery set:
75AH
Upper measurement threshold of
the battery set temperature: 80°C
Lower measurement threshold of
the battery set temperature: -20°
C
Upper alarm threshold of the
battery set temperature: 50°C
Lower alarm threshold of the
battery set temperature: 0°C
Temperature compensation
coefficient of the battery set: 80
mV
Charging mode of the battery:
automatic
Equalized charging voltage of
the battery: 56.5 V
Float charging voltage of the
battery: 53.5 V
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
3 Basic Configuration
Remarks
The selected type of the EPS30-4815AF
is Power4830 (Pwr4830).
-
The DIP switch on the EPS30-4815AF
is set to 4.
You can change the configuration by
running the power battery command
according to the actual requirements.
The MA5616 can be installed in the
F01E2OOE, F01E400, or F01S300
cabinet. A 26 AH battery set is
configured for the F01E200E cabinet, a
75 AH battery set is configured for the
F01E400 cabinet, and a 50 or 92 AH
battery set is configured for the
F01S300 cabinet.
NOTE
When a 92 AH battery set is configured for
the F01S300 cabinet, the charging current-
limiting coefficien of the battery must be set
to 0.1.
In this topic, the default settings are
adopted. You can run the power
charge command to modify parameters
according to actual conditions.