SmartAX MA5616 Multi-service Access Module
Configuration Guide
Item
Battery set
power-off
parameters
High-
temperature
power-off
parameters of
the battery
Rectifier unit
parameter
Environment
monitoring
parameters
External
extended
digital
parameter of
the power
Issue 04 (2011-10-30)
Data
Battery set power-off permission
status: permit
Battery set power-off voltage: 43
V
Battery high-temperature
power-off permission status:
forbid
Temperature for battery high-
temperature power-off: 53°C
Number of rectifier units: 2
Upper alarm threshold of the
temperature: 68°C
Lower alarm threshold of the
temperature: -5°C
Upper measurement threshold of
the temperature: 80°C
Lower measurement threshold of
the temperature: -20°C
Upper alarm threshold of the
humidity: 80% RH
Lower alarm threshold of the
humidity: 10% RH
Upper measurement threshold of
the humidity: 100% RH
Lower measurement threshold of
the humidity: 0% RH
Extended digital parameter ID: 1 -
Valid level of extended digital
parameter 1: low level
Name of extended digital
parameter 1: Fan
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
3 Basic Configuration
Remarks
You can change the configuration by
running the power charge command
according to the actual requirements.
You can change the configuration by
running the power charge command
according to the actual requirements.
The EPS30-4815AF supports up to two
rectifier units.
You can change the configuration by
running the power environment
command according to the actual
requirements.
When the low level represents the valid
level, the device does not report an
alarm in the case of low level.
It is a user-defined digital parameter and
is set according to the actual
requirements. The monitoring digital
parameter of the fan status sensor is set
to monitor the fan status.