Huawei SmartAX MA5616 Configuration Manual page 144

Multi-service access module
Table of Contents

Advertisement

SmartAX MA5616 Multi-service Access Module
Configuration Guide
Item
huawei(config)#display emu 0
EMU ID: 0
----------------------------------------------------------------------------
EMU name
EMU type
Used or not : Used
EMU state
Frame ID
Subnode
COM port
----------------------------------------------------------------------------
huawei(config)#interface emu 0
huawei(config-if-h831vesc-0)#esc digital 0 available-level low-level digital-alarm
5 name Temperature
huawei(config-if-h831vesc-0)#esc digital 1 available-level high-level digital-
alarm 1 name Door
huawei(config-if-h831vesc-0)#esc digital 2 available-level low-level digital-alarm
2 name Arrester
huawei(config-if-h831vesc-0)#esc digital 3 available-level low-level digital-alarm
5 name Fan
huawei(config-if-h831vesc-0)#display esc environment info
EMU ID: 0
---------------------------Digital environment info-------------------------
ID Name
0
2
----------------------------------------------------------------------------
huawei(config-if-h831vesc-0)#quit
huawei(config)#save
Issue 04 (2011-10-30)
Data
Name of digital parameter 2:
Arrester
User-defined alarm ID of
digital parameter 2: 2
Digital parameter ID: 3
Valid level of digital
parameter 3: low level
Name of digital parameter 3:
Fan
User-defined alarm ID of
digital parameter 3: 5
: H831VESC
: H831VESC
: Normal
: 0
: 1
: -
State
Temperature
Normal 0
Arrester
Normal 0
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Remarks
This digital parameter is set according to the
actual requirements. The monitoring digital
parameter of the lightning arrester status
sensor is set to monitor the arrester status.
When the lightning arrester is faulty, the
MA5616 reports an alarm.
In the F01S50 cabinet, digital parameter 3
does not take effect. In the F01S100 cabinet,
digital parameter 3 is used to monitor the
MDF.
When the low level represents the valid level,
the MA5616 does not report an alarm in the
case of low level.
This digital parameter is set according to the
actual requirements. The monitoring digital
parameter of the fan status sensor is set to
monitor the fan status.
When the fan is faulty, the MA5616 reports
an alarm.
ESC environment state
Value |ID Name
|1
Door
|3
Fan
3 Basic Configuration
State
Value
Alarm
0
Normal 0
133