SmartAX MA5616 Multi-service Access Module
Configuration Guide
Item
huawei(config)#emu add 2 POWER4830 0 4 RS485 POWER4830
huawei(config)#interface emu 2
huawei(config-if-power4830-2)#display power system parameter
EMU ID: 2
----------------------------------------------------------------------------
Charge control state: Automatic control
Equalizing voltage
Charge Lmt quotiety : 0.15
Battery number
battery temperature test upper :
temperature redeem quotiety
battery temperature alarm upper:
Battery off permit
AC over alarm volt
DC over alarm volt
Power module number : 2
module 0 address: 1
module 1 address: 2
Battery high-temperature-off permit
Battery high-temperature-off temperature: 53 C
----------------------------------------------------------------------------
huawei(config-if-power4830-2)#display power environment parameter
EMU ID: 2
------------------------------------------------------------------------------
AnalogID Name
Issue 04 (2011-10-30)
Data
User-defined alarm ID of
extended digital parameter 1: 11
Extended digital parameter ID: 3 -
Valid level of extended digital
parameter 3: low level
Name of extended digital
parameter 3: SPD
User-defined alarm ID of
extended digital parameter 3: 19
: 56.50V
: 1
: Permit
: 280V
: 58 V
module 0 switch state
module 1 switch state
0
Temperature
1
Humidity
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Remarks
When the fan is faulty, the MA5616
reports an alarm.
The meanings of the alarm IDs are as
follows:
1: AC voltage; 2: AC switch; 3: battery
voltage; 4: battery fuse; 5: load fuse; 6:
rectifier; 7: DC power; 8: room door; 9:
thief; 10: wiring ; 11: fan; 12: fire; 13:
smoke; 14: power supply; 15: water; 16:
diesel; 17: smell 18: air-condition; 19:
arrester; 20: DC voltage; 21 output
switch; 22: digital user-defined alarm
When the low level represents the valid
level, the device does not report an
alarm in the case of low level.
It is a user-defined digital parameter and
is set according to the actual
requirements. The monitoring digital
parameter of the SPD status sensor is set
to monitor the SPD status.
When the lightning arrester is faulty, the
MA5616 reports an alarm.
Power system information
Floating voltage
Equalizing time
Battery 0 capacity
80C
battery temperature test lower: -20C
: 80mV
50C
battery temperature alarm lower: 0C
Battery off voltage
AC lack alarm voltage : 180V
DC lack alarm voltage : 45 V
: On
: On
: Forbid
power environment configration parameter
AlmUpper AlmLower TestUpper TestLower Unit
50
0
80
80
10
100
3 Basic Configuration
: 53.50V
: 60 days
: 65
AH
: 43.00V
type
-20
C
Current
0
%R.H.
Current
143