Switch (Sxcbr/Sxswi); Bay Reserve (Qcrsv); Reservation Input (Resin); Logic Rotating Switch For Function Selection And Lhmi Presentation Slgapc - ABB RELION 650 Series Applications Manual

Transformer protection version 2.1
Hide thumbs Also See for RELION 650 Series:
Table of Contents

Advertisement

1MRK 504 158-UEN A
11.2.3.3

Switch (SXCBR/SXSWI)

tStartMove is the supervision time for the apparatus to start moving after a command
execution. When the time has expired, the switch function is reset, and a cause-code is given.
During the
state. When the time has expired, the switch function is reset, and a cause-code is given. The
indication of the mid-position at SCSWI is suppressed during this time period when the
position changes from open to close or vice-versa if the parameter
On in the SCSWI function.
If the parameter
new correct end position is reached. If the parameter is set to
output pulse remains active until the timer
tOpenPulse is the output pulse length for an open command. If AdaptivePulse is set to
Adaptive , it is the maximum length of the output pulse for an open command. The default
length is set to 200 ms for a circuit breaker (SXCBR) and 500 ms for a disconnector (SXSWI).
tClosePulse is the output pulse length for a close command. If AdaptivePulse is set to
Adaptive , it is the maximum length of the output pulse for an open command. The default
length is set to 200 ms for a circuit breaker (SXCBR) and 500 ms for a disconnector (SXSWI).
11.2.3.4

Bay Reserve (QCRSV)

The timer
cannot be done by requesting bay due to for example communication failure.
When the parameter
apparatus (x) in the bay, only the own bay is reserved, that is, the output for reservation
request of other bays (RES_BAYS) will not be activated at selection of apparatus x.
11.2.3.5

Reservation input (RESIN)

With the
installed in the SA system.
11.3
Logic rotating switch for function selection and LHMI
presentation SLGAPC
11.3.1

Identification

Function description
Logic rotating switch for function
selection and LHMI presentation
11.3.2

Application

The logic rotating switch for function selection and LHMI presentation function (SLGAPC) (or
the selector switch function block, as it is also known) is used to get a selector switch
functionality similar with the one provided by a hardware multi-position selector switch.
Application manual
tIntermediate time the position indication is allowed to be in an intermediate (00)
AdaptivePulse is set to Adaptive the command output pulse resets when a
tCancelRes defines the supervision time for canceling the reservation, when this
ParamRequestx ( x =1-8) is set to Only own bay res. individually for each
FutureUse parameter set to Bay future use the function can handle bays not yet
tOpenPulsetClosePulse has elapsed.
IEC 61850
IEC 60617
identification
identification
SLGAPC
-
SuppressMidPos is set to
Not adaptive the command
ANSI/IEEE C37.2
device number
-
Section 11
Control
M16675-3 v7
M16677-3 v3
M16678-3 v3
SEMOD114936-1 v4
SEMOD167845-2 v3
SEMOD114927-4 v6
173