Predefined protocol support function execution status check area

■Connection No.1 (Un\G8300 to Un\G8335)
The execution status of the predefined protocol support function is stored.
For addresses corresponding to connections after the connection No.2, refer to the following.
Page 336 List of buffer memory addresses
Address
Un\G8300
Un\G8301
Un\G8302
Un\G8303 to Un\G8317
Un\G8318
Un\G8319
Un\G8320 to Un\G8335
*1 The following table lists the verification result codes and causes of verification mismatch.
Stored value
Description
00H
Normal
01H
Insufficient receive data
10H
Data not matched
11H
ASCII-binary conversion error
12H
Data length error
30H
Data length size error
FFH
Verification not performed
Name
Protocol execution status
System area
Received data verification result (receive packet No.1)
Received data verification result (receive packet No.2 to 16)
Protocol execution count
Protocol cancellation specification
System area
Cause
The total packet size of receive data is smaller than that set in protocol data.
The receive data do not match the value set in protocol data.
When the code type setting is "ASCII Hexadecimal", data not in ASCII code are received.
The received length value exceeded 2046 bytes.
The Length value received from the external device does not match the actual length.
Description
Stores the status of the protocol being executed at

connection No.1.

0: Unexecuted
1: Waiting for transmission
2: Sending
3: Waiting for data reception
4: Receiving
5: Execution completed
Stores the verification results of receive packet No.1.
• Element No. where the verification result did not match
(b0 to b7)
0: Verification matched
1 to 32: Element No. where the verification result did not
match
FFH: Verification not performed
• The cause of mismatch (verification result code) (b8 to
*1
b15)
The configuration is the same as receive packet No. 1.
Stores the number of protocol executions in Connection
No.1.
0: Protocol not executed
1 to 65535: Number of executions (When the number
exceeds 65535, the value remains 65535.)
Cancels the protocol executed in Connection No.1.
0: No cancellation instruction
1: Cancellation request (set by user)
2: Cancellation completed (set by system)
Appendix 3 Buffer Memory
A
APPX
359