2.24 Protect the Drive during Failures
Drive Model
4389
4453
4568
4675
*1
Yaskawa recommends a fuse with a large rated current for applications with repeated loads.
132
Maximum Applicable
Maximum Applicable
Motor Output
kW (HP)
Input Voltage < 460 V
Input Voltage ≥ 460 V
200 (250)
220 (300)
250 (335)
315 (400)
YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual
Motor Output
Input Current Rating
kW (HP)
220 (300)
260 (350)
300 (400)
335 (450)
Semiconductor
Protection Fuse Rated
Current
A
Manufacturer: EATON/
Bussmann
373
FWH-1000A
410
FWH-1200A
465
FWH-1200A
FWH-1400A
584
FWH-1600A
*1