11.4 C: Tuning
Set C6-03 [Carrier Frequency Upper Limit], C6-04, and C6-05 [Carrier Freq Proportional Gain] to make the
carrier frequency change linearly with the output frequency.
Note:
The drive detects oPE11 [Carrier Frequency Setting Error] when these conditions are correct at the same time:
• C6-04 ≥ C6-03
• C6-05 ≥ 6
C6-05: Carrier Freq Proportional Gain
No.
Name
(Hex.)
C6-05
Carrier Freq
Proportional Gain
(0227)
Set C6-03 [Carrier Frequency Upper Limit], C6-04 [Carrier Frequency Lower Limit], and C6-05 to make the
carrier frequency change linearly with the output frequency.
C6-09: Carrier Freq at Rotational Tune
No.
Name
(Hex.)
C6-09
Carrier Freq at
Rotational Tune
(022B)
If you do Auto-Tuning to a high-frequency motor or low-impedance motor and set a low carrier frequency, oC
[Overcurrent] can occur. To prevent oC , you can set the carrier frequency to a high value, then set C6-09 = 1.
The procedure to set the carrier frequency when the A1-02 [Control Method Selection] setting changes.
• When A1-02 = 2 to 4 [OLV, CLV, or AOLV], set C6-02 = F [Carrier Frequency Selection = User Defined (C6-
03 to C6-05)] and then increase the value set to C6-03 [Carrier Frequency Upper Limit].
• When A1-02 = 5 to 7 [OLV/PM, AOLV/PM, or CLV/PM], use C6-02 to increase the carrier frequency.
0 : 5kHz
Note:
When A1-02 = 5, 6, or 7, the carrier frequency is 2 kHz.
1 : use C6-03
Note:
When A1-02 = 5, 6, or 7, the carrier frequency is the value set to C6-02.
774
V/f
CL-V/f
OLV
CLV
AOLV
Sets the proportional gain for the carrier frequency. Set C6-02 = F [Carrier
Frequency Selection = User Defined (C6-03 to C6-05)] to set this
parameter.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the Auto-Tuning carrier frequency. Usually it is not necessary to
change this setting.
YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Default
(Range)
Determined by C6-02
(0 - 99)
Default
(Range)
0
(0, 1)