11.10 n: Special Adjustment
n6-01: Online Tuning Selection
No.
Name
(Hex.)
n6-01
Online Tuning
Selection
(0570)
0 : Disabled
1 : Line-to-Line Resistance Tuning
The drive adjusts the motor line-to-line resistance during run. This procedure is applicable for speed values 6 Hz
and less. It also adjusts the motor resistance value to increase the overload capacity in the low speed range.
2 : Voltage Correction Tuning
The drive adjusts the output voltage during run to increase overload tolerance and minimize the effects of high
temperatures on speed precision.
Note:
Setting 2 is enabled only when b8-01 = 0 [Energy Saving Control Selection = Disabled].
n6-05: Online Tuning Gain
No.
Name
(Hex.)
n6-05
Online Tuning Gain
(05C7)
Expert
When you use a motor that has a large secondary circuit time constant, decrease the setting value.
If the drive detects oL1 [Motor Overload], increase the setting value in 0.1-unit increments.
n6-11: Online Resistance Tuning
No.
Name
(Hex.)
n6-11
Online Resistance
Tuning
(1B56)
Expert

n7: EZ Drive

The n7 parameters provide special adjustments for EZ Vector Control.
n7-01: Damping Gain for Low Frequency
No.
Name
(Hex.)
n7-01
Damping Gain for
Low Frequency
(3111)
Expert
Note:
• If oscillation occurs in the low speed range, increase the acceleration time or increase the setting value in 0.5-unit increments.
• To get starting torque with the setting for C4-01 [Torque Compensation Gain], decrease the setting value in 0.3-unit increments.
n7-05: Response Gain for Load Changes
No.
Name
(Hex.)
n7-05
Response Gain for
Load Changes
(3115)
Expert
1000
V/f
CL-V/f
OLV
CLV
AOLV
Sets the type of motor data that Online Tuning uses for OLV control.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the compensation gain when n6-01 = 2 [Online Tuning Selection =
Voltage Correction Tuning]. Usually it is not necessary to change this
setting.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the responsiveness for online resistor tuning. Set this parameter to
approximately 1.000 to enable the function. The function is disabled when
the value is 0.000.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the oscillation suppression gain for the low speed range.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the response gain related to changes in the load.
YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Default
(Range)
0
(0 - 2)
Default
(Range)
1.0
(0.1 - 50.0)
Default
(Range)
0.000
(0.000 - 1.000)
Default
(Range)
1.0
(0.1 - 10.0)
Default
(Range)
100
(10 - 1000)