If the load inertia is too large and the drive detects a fault after Inertia Tuning, decrease the setting. If the drive
detects a fault when T3-01 [Test Signal Frequency] is set to a low value, adjust this parameter.
T3-03: Motor Inertia
No.
Name
(Hex.)
T3-03
Motor Inertia
(0762)
The default setting is for a Yaskawa standard motor as shown in the motor inertia table. Actual values will be
different when you use induction motors or PM motors.
Note:
Capacities smaller than 37 kW are set in units of 0.0001 kgm
T3-04: System Response Frequency
No.
Name
(Hex.)
T3-04
System Response
Frequency
(0763)
If this input value is too high, it can cause oscillation.

T4: EZ Tuning

Use T4 parameters to input the data necessary for motor parameter Auto-Tuning when A1-02 = 8 [Control
Method Selection = EZ Vector Control]. These two modes are available:
Value set in T4-01
0
1
*1
When you use a PM motor or a synchronous reluctance motor, it is not necessary to use the setup wizard. The drive will use the rated
rotation speed and number of motor poles to automatically calculate the rated frequency.
T4-01: EZ Tuning Mode Selection
No.
Name
(Hex.)
T4-01
EZ Tuning Mode
Selection
(3130)
0 : Motor Parameter Setting
1 : Line-to-Line Resistance
YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual
V/f
CL-V/f
OLV
CLV
Sets the inertia of the motor. This value uses the test signal response to
calculate the load inertia.
2
. Capacities 37 kW and larger are set in units of 0.001 kgm
V/f
CL-V/f
OLV
CLV
This parameter uses the load inertia value from the Inertia Tuning process to
automatically calculate and set C5-01 [ASR Proportional Gain 1].
Operational overview
Follow the instructions in the
setup wizard on the keypad to
manually enter the necessary
motor parameters.
Do only line-to-line resistance
tuning.
V/f
CL-V/f
OLV
CLV
Sets the type of Auto-Tuning for EZOLV control.
Description
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
Description
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
Items input for tuning
• T4-02 [Motor Type Selection]
• T4-03 [Motor Max
Revolutions]
• T4-04 [Motor Rated
Revolutions]
• T4-05 [Motor Rated
Frequency]
• T4-06 [Motor Rated Voltage]
• T4-07 [Motor Rated Current]
• T4-08 [Motor Rated Capacity]
• T4-09 [Number of Poles]
Motor Rated Current (FLA)
Description
AOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
11.12 T: Auto-Tuning
Default
(Range)
Determined by o2-04,
C6-01, and E5-01
(0.0001 - 6.0000
2
kgm
)
2
.
Default
(Range)
10.0 Hz
(0.1 - 50.0 Hz)
Items tuned
• E9-01 [Motor Type Selection]
• E9-02 [Maximum Speed]
• E9-03 [Rated Speed]
• E9-04 [Base Frequency]
• E9-05 [Base Voltage]
• E9-06 [Motor Rated Current
(FLA)]
• E9-07 [Motor Rated Power
(kW)]
• E9-08 [Motor Pole Count]
• E9-09 [Motor Rated Slip]
• E9-10 [Motor Line-to-Line
Resistance]
E9-10 [Motor Line-to-Line
Resistance]
Default
(Range)
0
(0, 1)
1039
11