1F: Motor Overload Alarm (oL1)
Setting
Function
1F
Motor Overload
Alarm (oL1)
Note:
Refer to "L1-01: Motor Overload (oL1) Protection" for more information.
20: Drive Overheat Pre-Alarm (oH)
Setting
Function
20
Drive Overheat Pre-
Alarm (oH)
Note:
Refer to "L8-02: Overheat Alarm Level" for more information.
21: Safe Torque OFF
Setting
Function
21
Safe Torque OFF
Note:
EDM = External Device Monitor
ON : Safety stop state
Terminals H1-HC and H2-HC are OFF or released (safety stop state).
OFF : Safety circuit fault or RUN/READY
Terminal H1-HC or terminal H2-HC is OFF or released (safety circuit fault), or the two terminals are ON or have
short circuited (RUN/READY).
22: Mechanical Weakening Detection
Setting
Function
22
Mechanical
Weakening Detection The terminal activates when the drive detects mechanical weakening.
Note:
Refer to "Mechanical Weakening Detection Function" for more information.
2F: Maintenance Notification
Setting
Function
2F
Maintenance
Notification
Tells the user about the maintenance period for these items:
• IGBT
• Cooling fan
• Capacitor
• Soft charge bypass relay
Note:
Refer to "Alarm Outputs for Maintenance Monitors" for more information.
YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual
V/f
CL-V/f
OLV
CLV
AOLV
The terminal activates when the electronic thermal protection value of the motor overload
protective function is a minimum of 90% of the detection level.
V/f
CL-V/f
OLV
CLV
AOLV
The terminal activates when the drive heatsink temperature is at the level set with L8-02 [Overheat
Alarm Level].
V/f
CL-V/f
OLV
CLV
AOLV
The terminal turns on (safety stop state) when the safety circuit and safety diagnosis circuit are
operating correctly and when terminals H1-HC and H2-HC are off (released).
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
The terminal activates when drive components are at their estimated maintenance period.
11.8 H: Terminal Functions
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
11
905

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents