11.9 L: Protection Functions
L6-02: Torque Detection Level 1
No.
Name
(Hex.)
L6-02
Torque Detection
Level 1
(04A2)
Note:
• Set the torque detection level as a percentage of the drive rated output current in all control methods to set the mechanical weakening
detection level.
• You can also use an analog input terminal to supply the torque detection level. To enable this function, set H3-xx = 7 [MFAI Function
Select = Overtorque/Undertorque DetectLvl]. If you set L6-02 and H3-x = 7, the analog input is most important and the drive disables
L6-02.
L6-03: Torque Detection Time 1
No.
Name
(Hex.)
L6-03
Torque Detection
Time 1
(04A3)
L6-04: Torque Detection Selection 2
No.
Name
(Hex.)
L6-04
Torque Detection
Selection 2
(04A4)
The drive detects overtorque if the motor current or output torque is more than the level set in L6-05 [Torque
Detection Level 2] for the length of time set in L6-06 [Torque Detection Time 2]. The drive detects undertorque if
the motor current or output torque is less than the level set in L6-05 for the length the time set in L6-06.
0 : Disabled
The drive will not detect overtorque or undertorque.
1 : oL @ Speed Agree - Alarm only
The drive detects overtorque when the output frequency aligns with the frequency reference. Detection does not
occur during acceleration/deceleration. The drive outputs an oL4 [Overtorque Detection 2] and operation
continues.
2 : oL @ RUN - Alarm only
When the Run command is enabled, the drive constantly detects overtorque. The drive outputs an oL4 and
operation continues.
3 : oL @ Speed Agree - Fault
The drive detects overtorque when the output frequency aligns with the frequency reference. Detection does not
occur during acceleration/deceleration. The drive outputs an oL4 [Overtorque Detection 2] and operation stops.
4 : oL @ RUN - Fault
When the Run command is enabled, the drive constantly detects overtorque. The drive outputs an oL4 and
operation stops.
5 : UL @ Speed Agree - Alarm only
The drive detects undertorque when the output frequency aligns with the frequency reference. Detection does not
occur during acceleration/deceleration. The drive outputs a UL4 [Undertorque Detection 2] and operation
continues.
6 : UL @ RUN - Alarm only
When the Run command is enabled, the drive constantly detects undertorque. The drive outputs a UL4 and
operation continues.
7 : UL @ Speed Agree - Fault
The drive detects undertorque when the output frequency aligns with the frequency reference. Detection does not
occur during acceleration/deceleration. The drive outputs a UL4 and operation stops.
972
V/f
CL-V/f
OLV
CLV
AOLV
Sets the detection level for Overtorque/Undertorque Detection 1. In V/f
control, drive rated output current = 100% value. In vector control, motor
rated torque = 100% value.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the detection time for Overtorque/Undertorque Detection 1.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the speed range that detects overtorque and undertorque and the
operation of drives (operation status) after detection.
YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Default
(Range)
150%
(0 - 300%)
Default
(Range)
0.1 s
(0.0 - 10.0 s)
Default
(Range)
0
(0 - 8)