YASKAWA GA700 Technical Manual page 933

Hide thumbs Also See for GA700:
Table of Contents

Advertisement

H6-04: Terminal RP Function Bias
No.
Name
(Hex.)
H6-04
Terminal RP
Function Bias
(042F)
RUN
H6-05: Terminal RP Filter Time
No.
Name
(Hex.)
H6-05
Terminal RP Filter
Time
(0430)
RUN
H6-06: Terminal MP Monitor Selection
No.
Name
(Hex.)
H6-06
Terminal MP Monitor
Selection
(0431)
RUN
Note:
To use in through mode or when terminal MP is not used, set this parameter to 000 or 031.
When you use the pulse train monitor, make sure that you connect peripheral devices as specified by these load
conditions:
Incorrect connections can make the characteristics not sufficient or cause mechanical damage.
• Use the pulse train monitor as the sourcing output.
Output Voltage
5 V or more
8 V or more
10 V or more
Figure 11.119 Circuit Diagram When Used as the Sourcing Output
• Use the pulse train monitor as the sinking input
External Power Supply (V)
Sinking current (mA)
YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual
V/f
CL-V/f
OLV
CLV
Sets the bias used when the function in H6-01 [Terminal RP Pulse Train
Function] is input to terminal RP. Sets a value when the pulse train is 0 Hz.
V/f
CL-V/f
OLV
CLV
Sets the time constant for the primary delay filters of the pulse train input.
V/f
CL-V/f
OLV
CLV
Sets a function for pulse train monitor output terminal MP. Sets the "x-xx"
part of the Ux-xx monitor.
VRL(V)
Description
AOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
AOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
AOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Load Impedance (kΩ)
1.5 kΩ or more
4.0 kΩ or more
10 kΩ or more
12 VDC ± 10%, 15 VDC ± 10%
16 mA or less
11.8 H: Terminal Functions
Default
(Range)
0.0%
(-100.0 - 100.0%)
Default
(Range)
0.10 s
(0.00 - 2.00 s)
Default
(Range)
102
(000, 031, 101, 102,
105, 116, 501, 502,
801 - 809, 821 - 825,
831 - 839, 851 - 855)
11
933

Hide quick links:

Advertisement

Table of Contents
loading