11.8 H: Terminal Functions
C: Analog Terminal Enable Selection
Setting
Function
C
Analog Terminal
Enable Selection
ON : Terminal selected with H3-14 is enabled
OFF : Terminal selected with H3-14 is disabled
D: Ignore Speed Fdbk (V/f w/o Enc)
Setting
Function
D
Ignore Speed Fdbk
(V/f w/o Enc)
ON : Speed feedback control disable (V/f Control)
OFF : Speed feedback control enable (Closed Loop V/f Control)
E: ASR Integral Reset
Setting
Function
E
ASR Integral Reset
ON : P control
OFF : PI control
F: Not Used
Setting
Function
F
Not Used
Through Mode uses the signal input to the terminal as a digital input for the upper sequence through a
communication option or MEMOBUS/Modbus communications. This input signal does not have an effect on
drive operation.
10: Up Command
Setting
Function
10
Up Command
ON : Raises the frequency reference.
OFF : Holds the current frequency reference.
Note:
• If you only set the Up command or only set the Down command, the drive will detect oPE03 [Multi-Function Input Setting Err].
• If you set two or more of these functions at the same time, oPE03 occurs:
–Up/Down command
–Accel/Decel Ramp Hold
–Reference sample hold
–Offset Frequency 1, 2, 3 addition
–Up/Down 2 Command
• You can use the Up/Down command when the keypad is in REMOTE mode and when b1-01 ≠ 0 [Frequency Reference Selection 1 ≠
Keypad].
• The Up/Down command does not function when you use External Reference 1/2 Selection [H1-xx = 2] to switch to parameter b1-15
[Frequency Reference Selection 2].
When you input the Up command, the frequency reference increases. When you input the Down command, the
frequency reference decreases.
870
V/f
CL-V/f
OLV
CLV
AOLV
Sets the command that enables or disables the terminals selected in H3-14 [Analog Input Terminal
Enable Sel].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the command to disable speed feedback control and run the drive in V/f control or use speed
feedback from the encoder.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the command to reset the integral value and use PI control or P control for the speed control
loop.
V/f
CL-V/f
OLV
CLV
AOLV
Setting for terminals that are not being used or terminals being used in through mode.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the command to use a button to increase the drive frequency reference. You must also set
Setting 11 [Down Command].
YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM