11.8 H: Terminal Functions
9: Frequency Reference from Keypad
Setting
Function
9
Frequency Reference
from Keypad
ON : The keypad is the frequency reference source.
OFF : b1-01 or b1-15 [Frequency Reference Selection 1 or 2] is the frequency reference source.
A: Run Command from Keypad
Setting
Function
A
Run Command from
Keypad
ON : The keypad is the Run command source.
OFF : b1-02 or b1-16 [Run Command Selection 1 or 2] is the Run command source.
B: Torque Detection 1 (N.O.)
Setting
Function
B
Torque Detection 1
(N.O.)
ON : The output current/torque is more than the torque value set with L6-02 [Torque Detection
Level 1], or the level is less than the torque value set with L6-02 for longer than the time set with
L6-03 [Torque Detection Time 1].
Note:
• When L6-01 ≥ 5, the drive will detect when the output current/torque is less than the detection level of L6-02 for longer than the time
set in L6-03.
• Refer to "L6: Torque Detection" for more information.
C: Frequency Reference Loss
Setting
Function
C
Frequency Reference
Loss
Note:
Refer to "L4-05: Fref Loss Detection Selection" for more information.
D: Braking Resistor Fault
Setting
Function
D
Braking Resistor
Fault
E: Fault
Setting
Function
E
Fault
Note:
The terminal will not turn on for CPF00 and CPF01 [Control Circuit Error] faults.
F: Not Used
Setting
Function
F
Not Used
900
V/f
CL-V/f
OLV
CLV
AOLV
Shows the selected frequency reference source.
V/f
CL-V/f
OLV
CLV
AOLV
Shows the selected Run command source.
V/f
CL-V/f
OLV
CLV
AOLV
The terminal activates when the drive detects overtorque or undertorque.
V/f
CL-V/f
OLV
CLV
AOLV
The terminal activates when the drive detects a loss of frequency reference.
V/f
CL-V/f
OLV
CLV
AOLV
The terminal activates when the mounting-type braking resistor is overheating or when there is a
braking transistor fault.
V/f
CL-V/f
OLV
CLV
AOLV
The terminal activates when the drive detects a fault.
V/f
CL-V/f
OLV
CLV
AOLV
Use this setting for unused terminals or to use terminals in through mode. Also use this setting as
the PLC contact output via MEMOBUS/Modbus or the communication option. This signal does not
function if signals from the PLC are not configured.
YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
Description
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV