YASKAWA GA700 Technical Manual page 584

Hide thumbs Also See for GA700:
Table of Contents

Advertisement

10.12 n: Special Adjustment
No.
Name
(Hex.)
n8-41
HFI P Gain
(0568)
Expert
n8-42
HFI I Time
(0569)
Expert
n8-45
Speed Feedback
Detection Gain
(0538)
n8-47
Pull-in Current
Comp Filter Time
(053A)
n8-48
Pull-in/Light Load
Id Current
(053B)
n8-49
Heavy Load Id
Current
(053C)
Expert
n8-51
Pull-in Current @
Acceleration
(053E)
n8-54
Voltage Error
Compensation
(056D)
Time
Expert
n8-55
Motor to Load
Inertia Ratio
(056E)
n8-57
HFI Overlap
Selection
(0574)
n8-62
Output Voltage
Limit Level
(057D)
Expert
n8-65
Speed Fdbk Gain
@ oV Suppression Sets the gain of internal speed feedback detection suppression while
(065C)
Expert
n8-69
Speed Observer
Control P Gain
(065D)
Expert
584
Description
V/f
CL-V/f
OLV
CLV
AOLV
Sets the speed estimation response for high frequency injection.
Usually it is not necessary to change this setting.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the oscillation suppression gain of the speed estimation for high
frequency injection. Usually it is not necessary to change this
setting.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the internal speed feedback detection reduction unit gain as a
magnification value. Usually it is not necessary to change this
parameter.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the time constant the drive uses to align the pull-in current
reference value with the actual current value. Usually it is not
necessary to change this parameter.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the d-axis current that flows to the motor during run at constant
speed as a percentage where E5-03 [PM Motor Rated Current
(FLA)] = 100%.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the d-axis current to that the drive will supply to the motor to
run it at a constant speed with a heavy load. This parameter is a
percentage where E5-03 [PM Motor Rated Current (FLA)] = 100%.
Usually it is not necessary to change this setting.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the pull-in current that can flow during acceleration/
deceleration as a percentage where E5-03 [PM Motor Rated Current
(FLA)] = 100%.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the time constant that the drive uses when adjusting for voltage
errors.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the ratio between motor inertia and machine inertia.
0 : Below 1:10
1 : Between 1:10 and 1:30
2 : Between 1:30 and 1:50
3 : Beyond 1:50
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function that detects motor speed with high frequency
injection.
0 : Disabled
1 : Enabled
V/f
CL-V/f
OLV
CLV
AOLV
Sets the output voltage limit to prevent saturation of the output
voltage. Usually it is not necessary to change this setting.
V/f
CL-V/f
OLV
CLV
AOLV
the overvoltage suppression function is operating as a magnification
value. Usually it is not necessary to change this parameter.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the gain that the drive uses for speed estimation. Usually it is
not necessary to change this setting.
YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Default
Ref.
(Range)
3.0
1004
(1.0 - 100.0)
1.0
1004
(0.1 - 5.0)
0.80
1004
(0.00 - 10.00)
5.0 s
1004
(0.0 - 100.0 s)
30%
1005
(20 - 200%)
Determined by E5-
1005
01
(-200.0 - 0.0%)
Determined by A1-
1005
02
(0 - 200%)
1.00 s
1005
(0.00 - 10.00 s)
0
1006
(0 - 3)
0
1006
(0, 1)
200 V Class: 200.0
1007
V, 400 V Class:
400.0 V
(200 V Class: 0.0 -
230.0 V, 400 V
Class: 0.0 - 460.0
V)
1.50
1007
(0.00 - 10.00)
1.00
1007
(0.00 - 20.00)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents