YASKAWA GA700 Technical Manual page 561

Hide thumbs Also See for GA700:
Table of Contents

Advertisement

No.
Name
(Hex.)
H3-09
Terminal A2 Signal
Level Select
(0417)
H3-10
Terminal A2
Function Selection Sets a function for MFAI terminal A2.
(0418)
H3-11
Terminal A2 Gain
Setting
(0419)
RUN
H3-12
Terminal A2 Bias
Setting
(041A)
RUN
H3-13
Analog Input
FilterTime
(041B)
Constant
H3-14
Analog Input
Terminal Enable
(041C)
Sel
H3-16
Terminal A1 Offset
(02F0)
H3-17
Terminal A2 Offset
(02F1)
H3-18
Terminal A3 Offset
(02F2)
H3-40
Mbus Reg 15C1h
Input Function
(0B5C)
H3-41
Mbus Reg 15C2h
Input Function
(0B5F)
H3-42
Mbus Reg 15C3h
Input Function
(0B62)
H3-43
Mbus Reg Inputs
FilterTime Const
(117F)
H3-xx: MFAI Function Selections
Setting
Function
0
Frequency
Reference
1
Frequency Gain
YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual
Description
V/f
CL-V/f
OLV
CLV
AOLV
Sets the input signal level for MFAI terminal A2.
0 : 0-10V (LowLim=0)
1 : -10 to +10V (Bipolar Reference)
2 : 4 to 20 mA
3 : 0 to 20 mA
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
Sets the gain of the analog signal input to MFAI terminal A2.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the bias of the analog signal input to MFAI terminal A2.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the time constant to apply a primary delay filter to the MFAI
terminal.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the enabled terminal or terminals when H1-xx = C [MFDI
Function Select = Analog Terminal Enable Selection] is ON.
1 : Terminal A1 only
2 : Terminal A2 only
3 : Terminals A1 and A2
4 : Terminal A3 only
5 : Terminals A1 and A3
6 : Terminals A2 and A3
7 : Terminals A1, A2, and A3
V/f
CL-V/f
OLV
CLV
AOLV
Sets the offset level for analog signals input to terminal A1. Usually
it is not necessary to change this setting.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the offset level for analog signals input to terminal A2. Usually
it is not necessary to change this setting.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the offset level for analog signals input to terminal A3. Usually
it is not necessary to change this setting.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the MEMOBUS AI1 function.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the MEMOBUS AI2 function.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the MEMOBUS AI3 function.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the time constant to apply a primary delay filter to the
MEMOBUS analog input terminal.
V/f
CL-V/f
OLV
CLV
AOLV
The input value from the MFAI terminal set with this function becomes the master
frequency reference.
V/f
CL-V/f
OLV
CLV
AOLV
The drive multiplies the analog frequency reference with the input value from the MFAI
set with this function.
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
10.10 H: Terminal Functions
Default
Ref.
(Range)
2
915
(0 - 3)
0
915
(0 - 32)
100.0%
916
(-999.9 - +999.9%)
0.0%
916
(-999.9 - +999.9%)
0.03 s
916
(0.00 - 2.00 s)
7
916
(1 - 7)
0
917
(-500 - +500)
0
917
(-500 - +500)
0
917
(-500 - +500)
F
917
(4 - 2F)
F
917
(4 - 2F)
F
917
(4 - 2F)
0.00 s
918
(0.00 - 2.00 s)
Ref.
918
918
10
561