11.2 A: Initialization Parameters
The drive software contains the application presets shown below. Set A1-06 to align with the application to let the
drive automatically set the best parameter settings for the selected application. The drive saves parameters
frequently used for the application in parameters A2-01 to A2-16 [User Parameters 1 to 16] for easy configuration
and reference in [User Custom Parameters] in the main menu.
• Water supply pump
• Conveyor
• Exhaust fan
• HVAC fan
• Air compressor
• Crane (hoist)
• Crane (traveling)
Note:
• Before you set A1-06, make sure that you set A1-03 = 2220, 3330 [Initialize Parameters = 2-Wire Initialization, 3-Wire Initialization]
to initialize parameters.
• After you set A1-06 for a hoist application (A1-06 = 6 or 7), make sure that you do Auto-Tuning.
• It is not possible to change the A1-06 value. To set an application preset, first set A1-03 = 2220 to initialize parameters, then make a
selection to A1-06. If initializing all parameters will cause a problem, do not change the settings.
If you set A2-33 = 1 [User Parameter Auto Selection = Enabled: Auto Save Recent Parms] to set parameters to A2-17 to A2-32 [User
Parameters 17 to 32] automatically, the drive will reset these parameters when you change the A1-06 setting.
0 : General-purpose
The drive saves the parameters in
Table 11.3 Parameters Saved as User Parameters with the General-purpose Preset
User Parameter No.
A2-01
A2-02
A2-03
A2-04
A2-05
A2-06
A2-07
A2-08
A2-09
A2-10
A2-11
A2-12
A2-13
A2-14
A2-15
A2-16
A2-17
A2-18
A2-19
A2-20
A2-21
A2-22
A2-23
A2-24
A2-25
A2-26
680
Table 11.3
as user parameters.
Parameter No. Saved
A1-02
b1-01
b1-02
b1-03
C1-01
C1-02
C6-01
C6-02
d1-01
d1-02
d1-03
d1-04
d1-17
E1-01
E1-03
E1-04
E1-05
E1-06
E1-09
E1-13
E2-01
E2-04
E2-11
H4-02
L1-01
L3-04
YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual
Name
Control Method Selection
Frequency Reference Selection 1
Run Command Selection 1
Stopping Method Selection
Acceleration Time 1
Deceleration Time 1
Normal / Heavy Duty Selection
Carrier Frequency Selection
Reference 1
Reference 2
Reference 3
Reference 4
Jog Reference
Input AC Supply Voltage
V/f Pattern Selection
Maximum Output Frequency
Maximum Output Voltage
Base Frequency
Minimum Output Frequency
Base Voltage
Motor Rated Current (FLA)
Motor Pole Count
Motor Rated Power (kW)
Terminal FM Analog Output Gain
Motor Overload (oL1) Protection
Stall Prevention during Decel