Protect The Drive During Failures; Factory-Recommended Branch Circuit Protection - YASKAWA GA700 Technical Manual

Hide thumbs Also See for GA700:
Table of Contents

Advertisement

2.24

Protect the Drive during Failures

Factory-Recommended Branch Circuit Protection

Use branch circuit protection to protect against short circuits and to maintain compliance with UL61800-5-1.
Yaskawa recommends connecting semiconductor protection fuses on the input side for branch circuit protection.
Refer to
Table 2.30
to
Table 2.33
WARNING! Electrical Shock Hazard. Do not immediately energize the drive or operate peripheral devices after the drive blows
a fuse or trips an RCM/RCD. Wait for the time specified on the warning label at a minimum and make sure that all indicators are
OFF. Then check the wiring and peripheral device ratings to find the cause of the problem. Contact Yaskawa before energizing
the drive or peripheral devices if the cause is not known. Failure to obey can cause death or serious injury and damage to the
drive.
• 200 V class
Use the fuses specified in this document to prepare the drive for use on a circuit that supplies not more than
100,000 RMS symmetrical amperes and 240 Vac when there is a short circuit in the power supply.
• 400 V class
Use the fuses specified in this document to prepare the drive for use on a circuit that supplies not more than
100,000 RMS symmetrical amperes and 480 Vac when there is a short circuit in the power supply.
The built-in short circuit protection of the drive does not provide branch circuit protection. The user must provide
branch circuit protection as specified by the National Electric Code (NEC), the Canadian Electric Code, Part I
(CEC), and local codes.
Table 2.30 Factory-Recommended Branch Circuit Protection: 200 V Class (ND)
Drive Model
2004
2006
2010
2012
2018
2021
2030
2042
2056
2070
2082
2110
2138
2169
2211
2257
2313
2360
2415
*1
Yaskawa recommends a fuse with a large rated current for applications with repeated loads.
YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual
for the recommended fuses.
Maximum Applicable Motor
Output
kW (HP)
0.75 (0.75)
1.1 (1.5)
2.2 (3)
3 (4)
3.7 (5)
5.5 (7.5)
7.5 (10)
11 (15)
15 (20)
18.5 (25)
22 (30)
30 (40)
37 (50)
45 (60)
55 (75)
75 (100)
90 (125)
110 (150)
-

2.24 Protect the Drive during Failures

Input Current Rating
A
4.8
6.7
12.7
17
20.7
30
40.3
52
78.4
96
114
111
136
164
200
271
324
394
-
Semiconductor Protection
Fuse Rated Current
Manufacturer: EATON/
Bussmann
FWH-45B
FWH-45B
FWH-45B
FWH-100B
FWH-100B
FWH-100B
FWH-125B
FWH-150B
FWH-200B
FWH-225A
FWH-225A
FWH-250A
*1
FWH-225A
FWH-250A
*1
FWH-275A
FWH-300A
*1
FWH-275A
FWH-350A
*1
FWH-325A
FWH-450A
*1
FWH-600A
FWH-800A
FWH-1000A
-
129