F6-30: PROFIBUS-DP Node Address
No.
Name
(Hex.)
F6-30
PROFIBUS-DP Node
Address
(03CB)
Note:
• Be sure to set a node address that is different than all other node addresses.
• Node addresses 0, 1, and 2 are usually reserved for control, maintenance, and device self-diagnosis.
F6-31: PROFIBUS-DP Clear Mode Selection
No.
Name
(Hex.)
F6-31
PROFIBUS-DP Clear
Mode Selection
(03CC)
0 : Reset
Resets drive settings, for example frequency reference and I/O settings.
1 : Hold Previous State
The drive keeps the same status as before it received the command.
F6-32: PROFIBUS-DP Data Format Select
No.
Name
(Hex.)
F6-32
PROFIBUS-DP Data
Format Select
(03CD)
Note:
The H5-11 [Comm ENTER Command Mode] setting makes the RAM enter command necessary or not necessary to write parameters
over network communication. When F6-32 = 0, 1, or 2, the H5-11 setting does not have an effect. The RAM enter command is always
necessary to write parameters.
0 : PPO Type
1 : Conventional
2 : PPO (bit0)
This function operates when bit 0 and bit 4 in the register STW have values of 1 (operate). Refer to the
PROFIBUS-DP communication manual for more information.
3 : PPO (Enter)
4 : Conventional (Enter)
5 : PPO (bit0, Enter)
This function operates when bit 0 and bit 4 in the register STW have values of 1 (operate). Refer to the
PROFIBUS-DP communication manual for more information.
F6-35: CANopen Node ID Selection
No.
Name
(Hex.)
F6-35
CANopen Node ID
Selection
(03D0)
Note:
Be sure to set an address that is different than all other node addresses. Do not set this parameter to 0. Incorrect parameter settings will
cause AEr [Station Address Setting Error] errors and the L.ERR LED on the option will come on.
YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual
V/f
CL-V/f
OLV
CLV
AOLV
Sets the node address for PROFIBUS-DP communication. Restart the drive
after changing this setting.
V/f
CL-V/f
OLV
CLV
AOLV
Sets what the drive will do after it receives the Clear Mode command.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the data format of PROFIBUS-DP communication. Restart the drive
after changing this setting.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the node address for CANopen communication. Restart the drive after
changing this setting.
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
11.7 F: Options
Default
(Range)
0
(0 - 125)
Default
(Range)
0
(0, 1)
Default
(Range)
0
(0 - 5)
Default
(Range)
0
(0 - 126)
11
849