YASKAWA GA700 Technical Manual page 270

Hide thumbs Also See for GA700:
Table of Contents

Advertisement

4.3 UL Standards
Model
Terminals
R/L1, S/L2, T/L3, R1/
L11, S1/L21, T1/L31
U/T1, V/T2, W/T3
4675
-, +1
+3
*1
For IP20 protection, use wires that are in the range of applicable gauges.
*2
Remove insulation from the ends of wires to expose the length of wire shown.
*3
For wire gauges more than AWG 8, tighten to a tightening torque of 4.1 N∙m to 4.5 N∙m (36 lb∙in. to 40 lb∙in.).
*4
Terminals - and +1 have two screws. The Recommended Gauge is the wire gauge for one terminal.
*5
A junction terminal is necessary to connect a braking resistor unit (LKEB-series) to terminals B1 and B2.
Closed-Loop Crimp Terminals
To comply with UL standards on drive models 2257 to 2415 and 4208 to 4675, use UL-approved closed-loop
crimp terminals. Use the tools recommend by the terminal manufacturer to crimp the closed-loop crimp terminal.
Yaskawa recommends closed-loop crimp terminals from JST Mfg. Co., Ltd. and insulation caps from Tokyo DIP
Co., Ltd.
Comply with local standards for correct wire gauges in the region where the drive is used.
Contact Yaskawa or your nearest sales representative to order.
Refer to
Table 4.13
to select crimp terminals as specified by drive model and wire gauge.
Note:
To comply with UL standards, use only insulated crimp terminals or crimp terminals with insulation tubing. Use UL-Listed, vinyl-
coated insulated copper wires for operation with a continuous maximum permitted temperature of 75 °C at 600 V.
Recommended Gauge (AWG, kcmil)
R/L1
U/T1
Model
S/L2
V/T2
T/L3
W/T3
2004 -
-
2021
2030, 2042
-
2056
-
2070 -
-
2110
2138
-
2169, 2211
-
-
-
2257
2/0 × 2P
2/0 × 2P
-
270
Applicable
Gauge
Recommended
Gauge
Applicable
AWG, kcmil
Gauge
AWG, kcmil
2/0 - 300 × 4P
300 × 4P
(250 - 300 × 4P)
2/0 - 300 × 4P
300 × 4P
(250 - 300 × 4P)
3/0 - 400 × 4P
400 × 4P
(300 - 400 × 4P)
2 - 4/0 × 4P
4/0 × 4P
(4/0 × 4P)
2/0 - 300
2/0
Table 4.13 Closed-Loop Crimp Terminals and Insulation Caps
-, +1
+3
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
1/0 × 2P
-
-
-
4/0 × 2P
-
YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual
Wire
Stripping
(IP20
Length
*2
Size
)
*1
mm
-
-
-
-
-
(-)
Terminal
Screw
Terminal
Size
10
M4
8
M5
6
M6
6
M6
4
M6
4
M8
3
-
M10
-
-
Terminal Screw
Shape
M12
Hex self-locking nut
M12
Hex self-locking nut
M12
Hex self-locking nut
M12
Hex self-locking nut
M12
Hex bolt (slotted)
Crimping Tool
Crimp
Tool
Die Jaw
Model
Model
R5.5-4
YA-4
AD-900
R8-5
YA-4
AD-901
R14-6
YA-4
AD-902
R14-6
YA-4
AD-902
R22-6
YA-5
AD-953
R22-8
YA-5
AD-953
TD-224,
R38-10
TD-212
TD-225,
R60-10
TD-213
YF-1
YET-150-1
TD-227,
80-10
TD-214
TD-228,
R100-10
TD-214
Tightening
Torque
N∙m (lb∙in.)
35
(310)
35
(310)
35
(310)
35
(310)
32 - 40
(283 - 354)
Insula
tion Cap
Model
TP-005
TP-008
TP-014
TP-014
TP-022
TP-022
TP-038
TP-060
TP-080
TP-100