H2: Multi-Function Digital Output - YASKAWA GA700 Technical Manual

Hide thumbs Also See for GA700:
Table of Contents

Advertisement

11.8 H: Terminal Functions
7E: Reverse Rotation Identifier
Setting
Function
7E
Reverse Rotation
Identifier
ON : Reverse
Detects if the motor is rotating in the reverse direction.
OFF : Forward
Detects if the motor is rotating in the forward direction.
7F: PID Bi-Directional Enable
Setting
Function
7F
PID Bi-Directional
Enable
ON : Enabled
OFF : Disabled
90 to 97: DriveWorksEZ Digital Inputs 1 to 8
Setting
Function
90 to 97
DriveWorksEZ
Digital Inputs 1 to 8
Note:
You cannot set values 90 to 97 for inverse output.
9F: DWEZ Disable
Setting
Function
9F
DWEZ Disable
Note:
Set A1-07 = 2 [DriveWorksEZ Function Selection = Digital input] to use this function.
ON : Disabled
OFF : Enabled
101 to 19F: Inverse Input of 1 to 9F
Setting Value
Function
101 to 19F
Inverse Input of 1 to 9F
For example, to use the inverse input of E [ASR Integral Reset], set H1-xx = 10E.
Note:
You cannot use inverse input for all functions. Refer to

H2: Multi-function Digital Output

H2 parameters set the MFDO terminal functions.
H2-01 to H2-03 Terminal M1-M2, M3-M4, M5-M6 Function Selection
The drive has three MFDO terminals.
886
V/f
CL-V/f
OLV
CLV
AOLV
Sets the rotation direction of the motor when in Simple Closed Loop V/f Control method and F1-
21, F1-37 = 0 [Encoder Option Function Selection = A pulse detection], or when in Closed Loop
V/f Control method.
V/f
CL-V/f
OLV
CLV
AOLV
Sets operation of the PID Bi-Directional function.
V/f
CL-V/f
OLV
CLV
AOLV
Sets digital inputs used with DriveWorksEZ. Refer to the DriveWorksEZ Online Manual for more
information.
V/f
CL-V/f
OLV
CLV
AOLV
Sets operation of the DriveWorksEZ program saved in the drive.
Sets the function of the selected MFDI to operate inversely. To select the function, enter
"1xx", where the "xx" is the function setting value.
Table 11.59
Table 11.64
shows the default function settings for the terminals.
YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
for more information.