YASKAWA GA700 Technical Manual page 306

Hide thumbs Also See for GA700:
Table of Contents

Advertisement

5.3 MEMOBUS/Modbus Communications
Register No.
(Hex.)
Time Setting
Setting range: 0000 to 2359 (decimal), the default value at energize: 0000
3004
Set the hour and the minute in HHMM format.
• HH: 00 to 23 (decimal)
• MM: 00 to 59 (decimal)
Year and Day Setting
Setting range: 1600 to 9906 (decimal), the default value at energize: 1600
Set the year and the day of the week in YYDW format.
• YY: the last two digits of the year from 16 to 99 (decimal)
• DW: the day of the week
– Sunday: 00
3005
– Monday: 01
– Tuesday: 02
– Wednesday: 03
– Thursday: 04
– Friday: 05
– Saturday: 06
Date Setting
Setting range: 0101 to 1231 (decimal), the default value at energize: 0101
3006
Set the month and the date in MMDD format.
• MM: 01 to 12 (decimal)
• DD: 01 to 31 (decimal)
Set the Date Information
Setting range: 0 to 8 (decimal), the default value at energize: 8
3007
Set the values specified in 3004H to 3006H as the date and time.
• Command Data: 1
• Response Data: 0 (normal), 8 (fault)
Monitor Data
You can only read monitor data.
306
Description
YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents