7.3 Maintenance
Monitor No.
Component
U4-06
Soft charge bypass relay
U4-07
Alarm Outputs for Maintenance Monitors
You can use H2-xx [Multi-Function Digital Out] to send a message that tells you when a specified component is
near the end of its performance life estimate. Set the applicable value to H2-xx as shown in
component.
When the specified component is near the end of its performance life estimate, the MFDO terminals set for H2-xx
= 2F [Maintenance Notification] will turn ON, and the keypad will show an alarm that identifies the component
to replace.
Display
Alarm Name
Cooling Fan
LT-1
Maintenance
Time
Capacitor
LT-2
Maintenance
Time
SoftChargeBy
LT-3
passRelay
MainteTime
IGBT
LT-4
Maintenance
Time (50%)
IGBT
TrPC
Maintenance
Time (90%)
Related Parameters
Replace the component, then set o4-03, o4-05, o4-07, and o4-09 [Maintenance Setting] = 0 to reset the
Maintenance Monitor. If these parameters are not reset after the corresponding parts have been replaced, the
Maintenance Monitor function will continue to count down the performance life from the value that was reached
with the old part. If the Maintenance Monitor is not reset, the drive will not have the correct value of the
performance life for the new component.
Note:
The drive installation environment has an effect on the maintenance period.
No.
o4-03
Fan Operation Time Setting
o4-05
Capacitor Maintenance Setting
o4-07
Softcharge Relay Maintenance
Set
o4-09
IGBT Maintenance Setting
404
Shows the number of times the drive is energized as a percentage of the performance life
of the inrush circuit.
IGBT
Shows the percentage of the maintenance period reached by the IGBTs.
Table 7.9 Maintenance Period Alarms
Cause
The cooling fan is at 90% of its
performance life estimate.
The main circuit and control circuit
capacitors are at 90% of their
performance life estimate.
The soft charge bypass relay is at
90% of its performance life estimate.
The IGBTs are at 50% of their
performance life estimate.
The IGBTs are at 90% of their
performance life estimate.
Table 7.10 Maintenance Setting Parameters
Name
Sets the value from which to start the cumulative drive cooling fan operation time in
10-hour units.
Note:
When o4-03 = 30 has been set, the drive will count the operation time for the
cooling fan from 300 hours and U4-03 [Cooling Fan Ope Time] will show 300 h.
Sets the value from which to start the count for the main circuit capacitor
maintenance period as a percentage.
Sets as a percentage the value from which to start the count for the soft charge bypass
relay maintenance time.
Sets the value from which to start the count for the IGBT maintenance period as a
percentage.
YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual
Description
Solution
Replace the cooling fan, then set o4-03 = 0
[Fan Operation Time Setting = 0 h] to reset
the cooling fan operation time.
Replace the board or the drive.
Contact Yaskawa or your nearest sales
representative to replace the board.
Replace the board or the drive.
Contact Yaskawa or your nearest sales
representative to replace the board.
Check the load, carrier frequency, and output
frequency.
Replace the IGBTs or the drive.
Function
Table 7.9
for your
MFDO
(Setting
Value in H2-
xx)
2F
10