YASKAWA GA700 Technical Manual page 985

Hide thumbs Also See for GA700:
Table of Contents

Advertisement

L8-53: STPo Integration Time
No.
Name
(Hex.)
L8-53
STPo Integration
Time
(0473)
Expert
L8-54: STPo Id Diff Detection
No.
Name
(Hex.)
L8-54
STPo Id Diff
Detection
(0474)
Expert
0 : Disabled
1 : Enabled
L8-55: Internal DB TransistorProtection
No.
Name
(Hex.)
L8-55
Internal DB
TransistorProtection
(045F)
0 : Disable
Disables braking transistor protection.
Use this setting, if enabling the braking transistor can cause an rF [Braking Resistor Fault] in these conditions:
• With a regenerative converter, for example D1000.
• With a regenerative unit, for example R1000.
• When connecting braking resistor options to the drive, for example CDBR units.
• Without an internal braking transistor.
1 : Protection Enabled
Prevents damage to the internal braking transistor when using a braking transistor or optional braking resistors.
These models have a built-in braking transistor:
• 2004 to 2138
• 4002 to 4168
L8-56: Stall P @ Accel Activation Time
No.
Name
(Hex.)
L8-56
Stall P @ Accel
Activation Time
(047D)
Expert
Note:
If this value is too small, it can cause incorrect detection of STPo. If this value is too large, the drive will not detect STPo.
L8-57: Stall Prevention Retry Counts
No.
Name
(Hex.)
L8-57
Stall Prevention
Retry Counts
(047E)
Expert
YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual
V/f
CL-V/f
OLV
CLV
AOLV
Sets the length of time until the drive detects STPo after exceeding the value
of L8-51 [STPo I Detection Level].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the Id deviation detection function for STPo [Desynchronization
Error].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the protection function for the internal braking transistor.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the length time that the acceleration stall prevention function can
continue to operate before the drive detects an STPo [Desynchronization
Error].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the number of times the acceleration stall prevention function can
operate until speeds match before the drive detects an STPo
[Desynchronization Error].
11.9 L: Protection Functions
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Default
(Range)
1.0 s
(1.0 - 10.0 s)
Default
(Range)
1
(0, 1)
Default
(Range)
1
(0, 1)
Default
(Range)
5000 ms
(100 - 5000 ms)
Default
(Range)
10 times
(1 - 10 times)
11