n8-62: Output Voltage Limit Level
No.
Name
(Hex.)
n8-62
Output Voltage Limit
Level
(057D)
Expert
Set this parameter lower than the input power supply voltage.
n8-65: Speed Fdbk Gain @ oV Suppression
No.
Name
(Hex.)
n8-65
Speed Fdbk Gain @
oV Suppression
(065C)
Expert
Adjust this parameter in these conditions:
• If there is resonance or hunting when you use the overvoltage suppression function, increase the setting value.
• If motor response is low when you use the overvoltage suppression function, decrease the setting value in 0.05-
unit increments.
n8-69: Speed Observer Control P Gain
No.
Name
(Hex.)
n8-69
Speed Observer
Control P Gain
(065D)
Expert
n8-72: Speed Estimation Method Select
No.
Name
(Hex.)
n8-72
Speed Estimation
Method Select
(0655)
Expert
0 : Method 1
1 : Method 2
n8-74: Light Load Iq Level
No.
Name
(Hex.)
n8-74
Light Load Iq Level
(05C3)
Expert
Note:
• If n8-74 > n8-75 [Medium Load Iq Level (low)], the drive will detect oPE08 [Parameter Selection Error].
• The change is linear between n8-74 and n8-75 and the level of the pull-in current from n8-48 to n8-78 [Medium Load Id Current].
YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual
V/f
CL-V/f
OLV
CLV
AOLV
Sets the output voltage limit to prevent saturation of the output voltage.
Usually it is not necessary to change this setting.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the gain of internal speed feedback detection suppression while the
overvoltage suppression function is operating as a magnification value.
Usually it is not necessary to change this parameter.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the gain that the drive uses for speed estimation. Usually it is not
necessary to change this setting.
V/f
CL-V/f
OLV
CLV
AOLV
Selects the speed estimation method. Usually it is not necessary to change
this setting.
V/f
CL-V/f
OLV
CLV
AOLV
Set n8-48 [Pull-in/Light Load Id Current] to the level of the load current (q-
axis current) to be applied.
11.10 n: Special Adjustment
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Default
(Range)
200 V Class: 200.0 V,
400 V Class: 400.0 V
(200 V Class: 0.0 -
230.0 V, 400 V Class:
0.0 - 460.0 V)
Default
(Range)
1.50
(0.00 - 10.00)
Default
(Range)
1.00
(0.00 - 20.00)
Default
(Range)
1
(0, 1)
Default
(Range)
30%
(0 - 255%)