7.3

Maintenance

The drive Maintenance Monitors keep track of component wear and tell the user when the end of the estimated
performance life is approaching. The Maintenance Monitors prevent the need to shut down the full system for
unexpected problems. Users can set alarm notifications for the maintenance periods for these drive components:
• Cooling fan
• Electrolytic capacitor
• Soft charge bypass relay
• IGBT
Contact Yaskawa or your nearest sales representative for more information about part replacement.
Replaceable Parts
You can replace these parts of the drive:
• Control circuit terminal board
• Cooling fan, circulation fan
• Keypad
If there is a failure in the main circuit, replace the drive.
If the drive is in the warranty period, contact Yaskawa or your nearest sales representative before you replace
parts. Yaskawa reserves the right to replace or repair the drive as specified by the Yaskawa warranty policy.
WARNING! Electrical Shock Hazard. Do not examine, connect, or disconnect wiring on an energized drive. Before servicing,
disconnect all power to the equipment and wait for the time specified on the warning label at a minimum. The internal capacitor
stays charged after the drive is de-energized. The charge indicator LED extinguishes when the DC bus voltage decreases
below 50 Vdc. When all indicators are OFF, remove the covers before measuring for dangerous voltages to make sure that the
drive is safe. Failure to obey will cause death or serious injury.
Part Replacement Guidelines
Table 7.7
shows the standard replacement period for replacement parts. When you replace these parts, make sure
that you use Yaskawa replacement parts for the applicable model and design revision number of your drive.
Cooling fan
Electrolytic Capacitor
*1
*1
If there is damage to parts that you cannot repair or replace, replace the drive.
NOTICE: Estimated performance life based on specific usage conditions. These conditions are provided for the purpose of
replacing parts to maintain performance. Some parts may require more frequent replacement due to poor environments or
rigorous use. Usage conditions for estimated performance life: Ambient temperature: Yearly average of 40 °C (IP00/Open Type
enclosure) Load factor: 80% maximum Operation time: 24 hours a day
Monitors that Display the Lifespan of Drive Components
The drive keypad shows percentage values for the replacement parts to help you know when you must replace
those components. Use the monitors in
the component is at the end of its useful life and there is an increase risk of drive malfunction. Yaskawa
recommends that you check the maintenance period regularly to make sure that you get the maximum
performance life.
Monitor No.
Component
U4-03
Cooling fan
U4-04
U4-05
Electrolytic capacitor
YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual
Table 7.7 Standard Replacement Period
Part
Table 7.8
to check replacement periods. When the monitor value is 100%,
Table 7.8 Performance Life Monitors
Shows the total operation time of fans as 0 to 99999 hours. After this value is 99999, the
drive automatically resets it to 0.
Shows the total fan operation time as a percentage of the specified maintenance period.
Shows the total capacitor usage time as a percentage of the specified maintenance
period.

7.3 Maintenance

Standard Replacement Period
10 years
10 years
Description
7
403