H2 Mfdo Parameters - YASKAWA GA700 Technical Manual

Hide thumbs Also See for GA700:
Table of Contents

Advertisement

Note:
• If you use the function to output logical calculation results, you cannot set H2-01 to H2-03 = 1xx [Inverse Output of xx]. If you do, the
drive will detect oPE33 [Digital Output Selection Error ].
• You cannot set 0 [3-Wire Sequence] and 20 to 2F [External Fault] for H2-60, H2-63, and H2-66.
• When you do not use H2-60, H2-63, and H2-66, set them to F. The Through Mode function is not supported.

H2 MFDO Parameters

H2-01: Term M1-M2 Function Selection
No.
Name
(Hex.)
H2-01
Term M1-M2
Function Selection
(040B)
Note:
Set this parameter to F when not using the terminal or to use the terminal in through mode.
H2-02: Term M3-M4 Function Selection
No.
Name
(Hex.)
H2-02
Term M3-M4
Function Selection
(040C)
Note:
Set this parameter to F when not using the terminal or to use the terminal in through mode.
H2-03: Term M5-M6 Function Selection
No.
Name
(Hex.)
H2-03
Term M5-M6
Function Selection
(040D)
Note:
Set this parameter to F when not using the terminal or to use the terminal in through mode.
H2-06: Watt Hour Output Unit Selection
No.
Name
(Hex.)
H2-06
Watt Hour Output
Unit Selection
(0437)
This output is input to the Watt hour meter or PLC through a 200 ms pulse signal. This parameter sets the kWh
unit for each pulse output.
Note:
• When the power value is a negative value (regenerative state), the drive does not count Watt hours.
• When the control power supply to the drive is operating, the drive will keep the Watt hours. If a momentary power loss causes the drive
to lose control power, the Watt hour count will reset.
YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual
V/f
CL-V/f
OLV
CLV
Sets the function for MFDO terminal M1-M2.
V/f
CL-V/f
OLV
CLV
Sets the function for MFDO terminal M3-M4.
V/f
CL-V/f
OLV
CLV
Sets the function for MFDO terminal M5-M6.
V/f
CL-V/f
OLV
CLV
Sets the unit for the output signal when H2-01 to H2-03 = 39 [MFDO
Function Select = Watt Hour Pulse Output].
Figure 11.90 Example MFDO when Configured for Watt Hours
Description
AOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
AOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
AOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
AOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
11.8 H: Terminal Functions
Default
(Range)
0
(0 - 1A7)
Default
(Range)
1
(0 - 1A7)
Default
(Range)
2
(0 - 1A7)
Default
(Range)
0
(0 - 4)
11
889