2.15 Control I/O Connections

Set Sinking Mode/Sourcing Mode

Close the circuit between terminals SC-SP and SC-SN to set the sinking mode/sourcing mode and the internal/
external power supply for the MFDI terminals. The default setting for the drive is internal power supply sinking
mode.
NOTICE: Do not close the circuit between terminals SP and SN. Failure to obey will cause damage to the drive.
Mode
Internal Power Supply (Terminal SN-SP)
Sinking Mode
(NPN)
Sourcing Mode
(PNP)

Set Input Signals for MFAI Terminals A1 to A3

Use terminals A1 to A3 to input a voltage or a current signal. Set the signal type as shown in
DIP Switch Settings
Termi
Input
nal
Signal
Switch
Voltage
input
A1
S1-1
Current
input
Voltage
input
A2
S1-2
Current
input
114
Figure 2.114 Location of DIP Switch S1
Table 2.28 MFAI Terminals A1 to A3 Signal Settings
Setting
No.
V
0: 0 V to 10 V/0% to 100% (input impedance: 20 kΩ)
(Default)
1: -10 V to +10 V/-100% to 100%
H3-01
2: 4 mA to 20 mA/0% to 100%
I
3: 0 mA to 20 mA/0% to 100% (input impedance: 250 Ω)
0: 0 V to 10 V/0% to 100% (input impedance: 20 kΩ)
V
1: -10 V to +10 V/-100% to 100%
H3-09
I
2: 4 mA to 20 mA/0% to 100%
(Defaul)
3: 0 mA to 20 mA/0% to 100% (input impedance: 250 Ω)
YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual