11.8 H: Terminal Functions
H3-11: Terminal A2 Gain Setting
No.
Name
(Hex.)
H3-11
Terminal A2 Gain
Setting
(0419)
RUN
When 10 V (or 20 mA) is input, this parameter sets the reference quantity for the function set for terminal A2 as a
percentage.
Use this parameter and H3-12 [Terminal A2 Bias Setting] to adjust the characteristics of the analog input signal to
terminal A2.
H3-12: Terminal A2 Bias Setting
No.
Name
(Hex.)
H3-12
Terminal A2 Bias
Setting
(041A)
RUN
When 0 V (4 mA or 0 mA) is input, this parameter sets the bias for the function set for terminal A2 as a
percentage.
Use this parameter and H3-11 [Terminal A2 Gain Setting] to adjust the characteristics of the analog input signal to
terminal A2.
H3-13: Analog Input FilterTime Constant
No.
Name
(Hex.)
H3-13
Analog Input
FilterTime Constant
(041B)
Apply the primary delay filter to the analog input to enable an analog input signal without the use of high-
frequency noise components. An analog input filter prevents irregular drive control. Drive operation becomes
more stable as the programmed time becomes longer, but it also becomes less responsive to quickly changing
analog signals.
H3-14: Analog Input Terminal Enable Sel
No.
Name
(Hex.)
H3-14
Analog Input
Terminal Enable Sel
(041C)
Input signals do not have an effect on terminals not set as targets.
1 : Terminal A1 only
2 : Terminal A2 only
3 : Terminals A1 and A2
4 : Terminal A3 only
5 : Terminals A1 and A3
6 : Terminals A2 and A3
7 : Terminals A1, A2, and A3
Note:
• The ON/OFF operation of terminal Sx set in Analog Terminal Input Selection [H1-xx = C] has an effect on only the analog input
terminal selected with H3-14.
• When H1-xx ≠ C, the functions set to terminals A1 to A3 are always enabled.
916
V/f
CL-V/f
OLV
CLV
AOLV
Sets the gain of the analog signal input to MFAI terminal A2.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the bias of the analog signal input to MFAI terminal A2.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the time constant to apply a primary delay filter to the MFAI terminal.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the enabled terminal or terminals when H1-xx = C [MFDI Function
Select = Analog Terminal Enable Selection] is ON.
YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Default
(Range)
100.0%
(-999.9 - +999.9%)
Default
(Range)
0.0%
(-999.9 - +999.9%)
Default
(Range)
0.03 s
(0.00 - 2.00 s)
Default
(Range)
7
(1 - 7)