Note:
A1-02 [Control Method Selection] selects which parameter is the reference.
A1-02 Setting
0
V/f Control
1
Closed Loop V/f Control
2
Open Loop Vector Control
3
Closed Loop Vector Control
4
Advanced OpenLoop Vector Control
5
PM Open Loop Vector Control
6
PM Advanced Open Loop Vector
7
PM Closed Loop Vector Control
8
EZ Open Loop Vector Control
ON : Output frequency < value of E1-09 or b2-01.
OFF : Output frequency ≥ value of E1-09 or b2-01.
2: Speed Agree 1
Setting
Function
2
Speed Agree 1
Note:
• The motor rotation direction does not have an effect on the detection function.
• CLV control uses motor speed as the reference.
ON : The output frequency is in the range of "frequency reference ± L4-02."
OFF : The output frequency does not align with the frequency reference although the drive is
running.
3: User-Set Speed Agree 1
Setting
Function
3
User-Set Speed
Agree 1
YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual
Control Method
Figure 11.92 Zero Speed Time Chart
V/f
CL-V/f
OLV
CLV
AOLV
The terminal turns on when the output frequency is in the range of the frequency reference ± L4-02
[Speed Agree Detection Width].
Figure 11.93 Speed Agree 1 Time Chart
V/f
CL-V/f
OLV
CLV
AOLV
The terminal activates when the output frequency is in the range of L4-01 [Speed Agree Detection
Level] ± L4-02 [Speed Agree Detection Width] and in the range of the frequency reference ± L4-02.
11.8 H: Terminal Functions
Parameter Used as the Reference
E1-09
E1-09
b2-01
E1-09
E1-09
E1-09
E1-09
b2-01
E1-09
Description
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
Description
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
11
897