Note:
Set E9-01 = 0 [Motor Type Selection = Induction (IM)] before you set this parameter.
E9-10: Motor Line-to-Line Resistance
No.
Name
(Hex.)
E9-10
Motor Line-to-Line
Resistance
(11ED)
Note:
This value is the motor line-to-line resistance. Do not set this parameter with the single-phase resistance.
Stationary Auto-Tuning automatically sets this parameter. If you cannot do Stationary Auto-Tuning, use the test
report from the motor manufacturer. You can calculate the motor line-to-line resistance with one of these
formulas:
• E-type insulation: [the resistance value (Ω) shown on the test report at 75 °C] × 0.92
• B-type insulation: [the resistance value (Ω) shown on the test report at 75 °C] × 0.92
• F-type insulation: [the resistance value (Ω) shown on the test report at 115 °C] × 0.87
YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual
V/f
CL-V/f
OLV
CLV
AOLV
Sets the line-to-line resistance for the motor stator windings.
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
11.6 E: Motor Parameters
Default
(Range)
Determined by o2-04
(0.000 - 65.000 Ω)
819